3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
A–65
Ct14
1,2
What happens if the orCat value is not supported or invalid
DOns: control is rejected (Oper-
ObjectAccessDenied).
SBOns: control is rejected (Oper-
ObjectAccessDenied).
DOes:
control is rejected (Oper- ServiceError,
ObjectAccessDenied).
SBOes: control is rejected (SBOw- ServiceError,
ObjectAccessDenied).
orCat supported:
2 (station control), 3 (remote-control),
5 (automatic-station), 6 (automatic-remote)
Ct15
1,2
Does the IED accept a SelectWithValue / Operate with the same control
value as the current status value
Is this behaviour configurable
DOns: N
SBOns: N
DOes: N
SBOes: N
Configurable: N
Ct16
1,2
Does the IED accept a select/operate on the same control object from 2
different clients at the same time
DOns: N
SBOns: N
DOes: Y
SBOes: N
Ct17
1
Does the IED accept a Select/SelectWithValue from the same client when
the control object is already selected (Tissue #334)
SBOns: N
SBOes: N
Ct18
1,2
Is for SBOes the internal validation performed during the SelectWithValue
and/or Operate step
SelectWithValue and Operate
Ct19
-
Can a control operation be blocked by Mod=Off or [On-]Blocked
(Compare PIXIT-Sr5)
Deprecated
Ct20
1,2
Does the IED support local / remote operation
Y (Only for XCBR)
Ct21
1,2
Does the IED send an InformationReport with LastApplError as part of the
Operate response- for control with normal security
SBOns: N
DOns: N
Ct22
2
How to force a "parameter-change-in-execution
"SBOns:Not Applicable
SBOes:Not Applicable
Ct23
1,2
How many SBOns/SBOes control objects be selected at the same time?
SBOns: n = "1"
SBOes: n = "1"
Ct24
1,2
Does the DUT support any operate timeout > 0
Y
Ct25
1,2
When CDC=DPC is supported, is it possible to have DPC (Controllable
Double Point) go to the intermediate state? (00)
N