Chapter 2: Installation and wiring
Vigilant VS1 and VS2 Technical Reference Manual
57
Cabinet wire routing
Using the diagram below, keep power-limited wiring in the shaded
area and nonpower-limited wiring in the unshaded area at all times.
Cabinet wire routing
00:00:00 01/01/07
,
[1]
[1]
Power-limited only when connected to a power-limited source. If
connected to a nonpower-limited source, all wiring on terminal
block TB3 must be FPL, FPLP, FPLR rated wire or equivalent, in
accordance with the NFPA 70
National Electric Code
and routed
separate from all power-limited wiring.