Chapter 1: System operation
Vigilant VS1 and VS2 Technical Reference Manual
15
Events with event messages
Event type
LCD display
Printer [1]
Alarm Active
type
reporting
Input
smoke
Alarm
active
SMK
ACT
Input smoke verified
Alarm active
SMK ACT
Input heat
Heat alarm
HEAT ACT
Input heat rate of rise
Heat alarm
HEAT ACT
Input duct alarm
Alarm active
DUCT ACT
Input pull station
Pull station alarm
PULL ACT
Input water flow
Water flow
WFLW ACT
Input water flow retard
Water flow
WFLW ACT
Zone alarm
Alarm active
ALRM ACT
Zone water flow
Alarm active
ALRM ACT
Supervisory
type
reporting
Input duct alarm
Supervisory
DUCT ACT
Zone
supervisory Supervisory
SUPV
ACT
Input supervisory latching
Supervisory
SUPV ACT
Input supervisory nonlatching
Supervisory
SUPV ACT
Monitor type reporting
Zone monitor
Monitor
MON ACT
Input
monitor
Monitor
MON
ACT
Prealarm
reporting
Pre-alarm PALM
ACT
Alarm verify reporting
Alarm verify
ALMV ACT
Maintenance
alert
reporting
Maint. alert
MANT ACT
Trouble
All devices
Trouble
TRBL ACT
Disable
All devices
Disable
DSBL ACT
Test
All devices
Test
TEST ACT
[1] See "Printout examples" below for an example of how events are printed.
Printout examples
Event information is printed each time an event takes place
provided a printer is connected to your system. The following is an
example of what the event information looks like on the printout
and a description of each piece of information printed for an event.