Chapter 1: System operation
16
Vigilant VS1 and VS2 Technical Reference Manual
Annunciator event
TRBL ACT | 18:00:07 01/01/2007 A:008
Annunciator 08
Description:
TRBL ACT = Trouble event
18:00:07 01/01/2007 = Time and date the event took place
A:008 = Annunciator 08
Annunciator 08 = Label (could be the default label or a custom label)
Internal event (panel or loop event)
MON ACT | 18:00:18 01/01/2007 E:010
Loop 2 Initializing
Description:
MON ACT = Monitor event
18:00:18 01/01/2007 = Time and date the event took place
E:010 = Event 010 (see "Event ID numbers and descriptions")
Loop 2 initializing = Label (could be the default label or a custom
label)
Zone event
ALRM ACT | 18:00:34 01/01/2007 Z:008
Zone 08
Description:
ALRM ACT = Alarm event
18:00:34 01/01/2007 = Time and date the event took place
Z:008 = Zone 08
Zone 08 = Label (could be the default label or a custom label)
Device event
ALRM ACT | 18:00:34 01/01/2007 L:1 D:128
Loop 1 Device 128
Description:
ALRM ACT = Alarm event
18:00:34 01/01/2007 = Time and date the event took place
L:1 = Loop 1
D:128 = Device 128
Loop 1 Device 128 = Label (could be the default label or a custom
label)