Chapter 3: Programming
Vigilant VS1 and VS2 Technical Reference Manual
121
2 wire verify Class A: Allows for the monitoring of two-wire conventional smoke detectors in a
Class A circuit (that require alarm verification)
Audible: Assigned to NACs connected to audible notification appliances that turn off when
Signal Silence is pressed
Visible: Assigned to NACs connected to visible notification appliance that do not turn off when
Signal Silence is pressed
Relay module
Relay nonsilence: For the connection of relay devices that do not follow signal silence.
Relay with silence: For the connection of relay devices that follow signal silence.
Loop Configuration
Zone
Correlation Groups
Device
⇩
Device
Loop 01<>
⇩
Device
Number 001
Loop 01 Device 001
⇩
Device 001
Zone 01<>
Label <>
Correlation Groups
⇩
To program a device:
1. Access the loop configuration options menu. See "Loop
configuration options."
2. Choose
Device.
3. Choose the loop the device is on. Note: If your panel only has
one loop, the loop selection screen does not display. Go to the
next step.
4. Choose the device (address) you want to configure. For the
250/500 point panel, addresses 1 to 125 are detectors and
addresses 126 to 250 are modules.
Note:
The two lines below the device number line on the screen
are the device label.
5. Program each device in your system using the "Device
programming options" table above.
Note:
If you chose a dual address device, both addresses for
the device are displayed on the screen (e.g. 001/002). The first
address listed is the device address you are programming.
When you pick the second address to program, both addresses
are still displayed but in reverse order (e.g. 002/001).
Note:
Depending on the type of device you are programming,
some of the options in the table below may not be available.
6. When you finish programming each option, choose Save.
7. Continue programming your system or press Menu to exit
menu mode.
Device 001
Base Follow Device<>
Type Smoke<>
Save