Chapter 1: System operation
38
Vigilant VS1 and VS2 Technical Reference Manual
Disabling a panel event
Some panel events can be disabled. For example, you may want to
disable the “battery missing” event if you are performing
maintenance on the panel and plan on disconnecting the battery.
When you disable an event, the event is not displayed on the LCD
display when it activates. When you disable an event:
• The common Disable LED turns on
• The common Trouble LED flashes and the panel goes into a
trouble state
• The common trouble relay changes state
• The disabled points and active points counters on the LCD
display increment
• A message indicating the event that is disabled is displayed on
the LCD display
Note:
Not all panel events can be disabled. Panel events that cannot
be disabled are labeled as "forbidden." The following panel events
can be disabled:
• Ground fault (event ID 034)
• Battery charger (event ID 035)
• Battery low (event ID 036)
• Battery missing (event ID 037)
• AC power (event ID 038)
• System AC power (event ID 041)
• Aux. power 1 (event ID 039)
• Aux. power 2 (event ID 040)
• Dialer line 1 fault (event ID 045)
• Dialer line 2 fault (event ID 046)
• Net receiver communication fault (event ID 051)
Reports
Test
Control
Program
⇩
To disable an event:
1. Press the Menu button.
2. Choose
Control.
3. Enter your password (the minimum of a level one password is
required).
4. Choose
Enable/Disable.
Enter Password
0000