CFN Series System
9-4
03/07/03
PUMP CONTROL UNIT(S)
+5 VDC Measurement
1.
Turn off the AC and DC power switches on the supply assembly.
2.
Locate the connector labeled POWER in the upper left-hand corner of the motherboard.
Remove the black plastic cover.
3.
Turn on the AC and DC power switches.
4.
Measure the
+5 VDC
between the orange (+) and black (-) wires. The voltage should be
+4.95 to +5.05 VDC.
5.
Measure the
+12 VDC
between the red (+) and black (-) wires. The voltage should be
+11.50 to +15.50 VDC depending on the type and number of pulsers and the number of
relays energized.
6.
Measure the
POWER FAIL
between the yellow (+) and black (-) wires. The voltage should
be +4.75 to +5.05 VDC.
NOTE:
There are no adjustments for these voltages.
7.
Turn off the AC and DC power switches.
8.
Replace the black plastic cover on the
connector and turn the AC and DC
power switches back on.
Содержание CFN Series
Страница 1: ...CFN SERIES SITE CONTROLLER II ISLANDER II START UP MANUAL C01665 GASBOY INTERNATIONAL LLC ...
Страница 2: ......
Страница 8: ...CFN Series System Contents 4 03 07 03 ...
Страница 24: ...CFN Series System 2 12 03 07 03 ...
Страница 25: ...Site Information 03 07 03 2 13 ...
Страница 26: ...CFN Series System 2 14 03 07 03 ...
Страница 38: ...CFN Series System 4 6 03 07 03 ...
Страница 56: ......
Страница 58: ......
Страница 72: ......
Страница 82: ...CFN Series System 9 10 03 07 03 ...
Страница 104: ...CFN Series System 12 12 03 07 03 ...
Страница 108: ...CFN Series System 13 4 03 07 03 ...