GARDINER TECHNOLOGY Gardtec 800 Скачать руководство пользователя страница 30

Page 

57

Page 

56

GARDTEC 

800 Series

Programming

Option No/

Description

Default

Gardtec 

800 Series Programming Guide

Available Options

23

No. Of

Bell Arms

99

Activations

(99)

00 - 99 Activations

Note: If this option is programmed to 0 the Bell will not activate

24

[Area1] Bell

Ring Time

20

Minutes

(20)

00 - 99 Minutes

Note: If this option is programmed to 0 the Bell will not activate

Note: Local environmental legislation should be checked

25

[Area1] Bell

Delay Time

00

Minutes

(00)

00 - 99 Minutes

Note: Bell delay is overridden in the event of a linefault

26

Bell

Type

SAB

(01)

(00) SCB

(01) SAB

Note: All Gardiner Technology Bell Boxes (including SCB types) should

use the (01) SAB setting.

27

Bell Tamper

Ring

On

(01)

(00) Off

(01) On

28

Entry 

Time 1

30

Seconds

(30)

00 - 99 Seconds

29

Entry 

Time 2

10

Seconds

(10)

00 - 99 Seconds

30

Digi

Start Delay

00

Seconds

(00)

00 - 99 Seconds

Note: Digi Start Delay applies to Part Set system

31

D1 Output

Mode

Off

(00)

(00) Off

(01) Zone Tamper

(02) General Tamper

(03) Alert

(04) Fire

(05) Part-Set

(06) Open/Close

(07) Panic

(08) Alarm

(09) Alarm B

(10) Alarm Abort

(11) 12V Power Fail

(12) Watchdog

(13) Mains Fail

(14) Area 1 Alarm

(15) Area 2 Alarm (16) Area 3 Alarm

(17) O/C Area 1

(18) O/C Area 2

(19) O/C Area 3

(20) O/C Cleaner

(21) Alrm B Area1 (22) Alarm B Area2

(23) Alarm B Area 3

(24) Alrm Abort A1(25) Alarm Abort A2

(26) Alarm Abort A3

(27) Panic Area 1 (28) Panic Area 2

(29) Panic Area 3

(30) Fire Area 1

(31) Fire Area 2

(32  Fire Area 3

32

D2 Output

Mode

Off

(00)

As D1 Output Mode (Option 31)

33

Digi Output

Start

Negative

Start

(01)

(00) Positive Start (01) Negative Start

Note: All Digi outputs (including D1 D2) are open collector outputs with

10 Ohm resistor in series, some Digis may require 6K8 pullups

GARDTEC 

800 Series

Programming

11

Final Set

Delay

03

Seconds

(03)

00 - 99 Seconds

Option No/

Description

Default

Gardtec 

800 Series Programming Guide

Available Options

12

[A1] Full Set

Exit Time

30

Seconds

(30)

00 - 99 Seconds

13

[A1] Part1

Exit Time

30

Seconds

(30)

00 - 99 Seconds

14

[A1] Part2

Exit Time

30

Seconds

(30)

00 - 99 Seconds

15

[A1] Part3

Exit Time

30

Seconds

(30)

00 - 99 Seconds

16

[A1] Full Set

Mode

Time

(03)

(00) Exit Terminator Button

(01) Entry/Exit Door

(02) Time + Entry/Exit Door

(03) Time

17

[A1] Part1

Set Mode

Time

(03)

(00) Exit Terminator Button

(01) Entry/Exit Door

(02) Time + Entry/Exit Door

(03) Time

18

[A1] Part2

Set Mode

Time

(03)

(00) Exit Terminator Button

(01) Entry/Exit Door

(02) Time + Entry/Exit Door

(03) Time

19

[A1] Part3

Set Mode

Time

(03)

(00) Exit Terminator Button

(01) Entry/Exit Door

(02) Time + Entry/Exit Door

(03) Time

20

Alert 1

Mode

Off

(03)

(00) Fire

(01) P.A

(02) Alert 

(03) Off

Note: This feature must be enabled using option No.56

21

Alert 2

Mode

Off

(03)

(00) Fire

(01) P.A

(02) Alert 

(03) Off

Note: This feature must be enabled using option No.57

22

Keyswitch/

No of RKPs

No K/S

1 Keypad

(01)

(Left Digit LED)

(Right Digit LED)

(00) No  Keyswitch

1 - 4 Number of Keypads

(01) Biased Keyswitch
(02) Normal Keyswitch
(03) Locked

4344R12.qxd  03/09/99 11:09  Page 56

Содержание Gardtec 800

Страница 1: ......

Страница 2: ......

Страница 3: ...nt now understanding the Gardtec 800 Series will prove to be a great time saver for the future It must be stressed that the Gardtec 840 is one system that is capable of being split into three areas Un...

Страница 4: ...This will set the system or area and remove the cleaner zones If a cleaner code is now entered the cleaner zones will also be set If a cleaner code is entered when the system is fully set or area set...

Страница 5: ...use of an alarm is through a zone tamper the description will be shortened to 13 characters on the display the last three characters being replaced with space T The zone descriptor is displayed whilst...

Страница 6: ...ter than 3 metres 1metre for MiniACE The metal version of the master control panel has ample trunking and conduit entries at the top and the bottom of the housing in addition to these entries there is...

Страница 7: ...to be mounted within the panel see Fig 1 Contour keypads are supplied as a complete g designed to allow mounting in one of three positions These are he left See Fig 2a Use fixing points A B D E placi...

Страница 8: ...g 4 Gardtec 800 Series LED Compact The base should be fastened to the wall in three positions using 30mm x No 6 screws and suitable rawl plugs Fig 4a Contour RKP Lower Flap to reveal single cover fixi...

Страница 9: ...he Gardtec 800 Series should be as shown in Fig 6 Fig 6 Warning the Gardtec 800 Series control panels MUST BE EARTHED Consumer Unit 3A Unswitched Fused Spur Control Panel Mains Terminal Block Mains Tw...

Страница 10: ...is situated on the bottom edge of the PCB towards the right hand side Wiring to the RKP s is terminal to terminal as shown in the following illustrations Fig 9 Single RKP wiring NOTE RKP terminal pos...

Страница 11: ...r link removed each ACE key fob will occupy one user code from the system this is termed as high security mode With the jumper link in position the ACE will occupy one user code from the system but up...

Страница 12: ...ower is applied to the unit with this jumper in position the memory contents will be erased When the unit is first powered up this jumper should be in position for at least 5 seconds After this initia...

Страница 13: ...peration is dependent on how the keyswitch option is programmed refer to Programmable Options Description and also see Remote Reset Note The Gardtec840 may be programmed to use zones for keyswitch set...

Страница 14: ...e 25 REMOTE RESET Note This option may use the Linefault or KS terminal The Line Fault or the K S terminal dependant on option 127 Remote Reset Source also doubles as the Remote Reset input normally f...

Страница 15: ...em Gardtec 840 Main PCB If the Gardtec Modem is used basic system configuration is available by defaulting the system using 5 5 YES NO Further details are given in the Gardtec Modem manual Page 26 gic...

Страница 16: ...panel must be taken into consideration SPKR SP SPKR SP Page 28 12V when the system is set and low 0V when the system is his terminal would be the latch signal for PIRs and Shockgards f 50mA 1 al is p...

Страница 17: ...3C 4 4B 4D 4Q Encapsulated SAB Strobe Note Terminal positions may change dependent on model R T1 T2 0V 12V S SET STR BATTERY TMP REAR 12V BELL SW RET TAMPER SUPPLY SW SAB BELL BELL LATCH STROBE TMP H...

Страница 18: ...xit terminator zone must be AZ zone Setting Mode should be programmed for ET Note AZ zones are ve TZ zones are ve To comply with BS4737 alarm and tamper loops should be oposite polarity Any unused zon...

Страница 19: ...d for ET Note AZ zones are ve TZ zones are ve To comply with BS4737 alarm and tamper loops should be oposite polarity Any unused zones may be programmed to off and the factory fitted link can be remov...

Страница 20: ...rs per loop using EOL Note Resistor Colour Codes Are 4K7 Yellow Purple Red with gold tolerance band EOL Resistor 6K8 Blue Grey Red with gold tolerance band Bypass Resistor Note All unused zones should...

Страница 21: ...SCLK SCLK The expander cards may also be wired back to the onboard expander card in Star format each expander card wired back individually Alternatively all the zone expander cards may be wired to th...

Страница 22: ...816 Expander Card 2 12V 0V SADOUT SCLK GARDTEC 800 Series GARDTEC 800 Series Wiring Connections Zone Wiring Zone Numbering No of No of No of Onboard Zones ZEX 1 Zones ZEX 2 Zones O B ZEX1 ZEX2 AZ1 AZ8...

Страница 23: ...Tamper Zone 53 Zone 57 Zone 57 TZE4 Tamper Zone 54 Zone 58 Zone 58 Note All AZE zones are ve and all TZE zones are ve GARDTEC 800 Series Wiring Connections Card Ident Zone Allocation der cards has ei...

Страница 24: ...r in position 5 840 only e Mode 2 Wire Mode 2 Wire EOL Mode ne 61 Zone 61 Zone 61 ne 62 Zone 62 Zone 62 ne 63 Zone 63 Zone 63 ne 64 Zone 64 Zone 64 Zone 61 Zone 65 Zone 65 Zone 62 Zone 66 Zone 66 Zone...

Страница 25: ...2 ID Biscuit Wiring Diagram Full wiring details are supplied with the ID Expander Board Zone No s 21 50 are on ID card 1 SAD1 Zone No s 51 80 are on ID card 2 SAD2 Fig33 Detector Using Wired ID Biscui...

Страница 26: ...refer to user manual for more details 2 For printing the Program Review engineer function Pressing 1 whilst in the engineer option Program Review will start the printer 3 For Real Time Printing When...

Страница 27: ...fice Door Area 1 ss Sales Office PIR Area 1 Exit Distribution Door Area 2 ss Distribution PIR Area 2 Exit Stores Door Area 3 ss Stores PIR Area 3 Exit Reception Door Areas 1 3 ss Reception PIR Areas 1...

Страница 28: ...ng of the system Exit Mode must be programmed for ET or Time ET Monitor Will write to the log once only in any one set or unset unless chime is allocated then all activations are written to the log GA...

Страница 29: ...n the Gardtec 800 Series control panel we strongly advise that an LCD keypad is used for programming Note Throughout this section all reference to settings and defaults applicable to LED only displays...

Страница 30: ...Fail 14 Area 1 Alarm 15 Area 2 Alarm 16 Area 3 Alarm 17 O C Area 1 18 O C Area 2 19 O C Area 3 20 O C Cleaner 21 Alrm B Area1 22 Alarm B Area2 23 Alarm B Area 3 24 Alrm Abort A1 25 Alarm Abort A2 26 A...

Страница 31: ...or zone attributes Note Refer to option 71 for Area and Chime attributes 52 Test Part Sets Cleaner Off Test 00 Left Digit LED Right Digit LED 0 Full Set 0 Off Test 1 Part 1 Set 1 On Test 2 Part 2 Set...

Страница 32: ...1 Area Programming Chime Forced Walk Test Allocation For LED Only Displays Area 1 FWT Off Chime Off 00 Left Digit LED 1 0 Area 1 1 Area 2 2 Areas 1 2 3 Area 3 4 Areas 1 3 5 Areas 2 3 6 Areas 1 2 3 Rig...

Страница 33: ...816 options are referred from options 1 44 83 Output Expander Modes 840 For LED Prompt is n Enter output No 1 16 then YES To change setting press NO then enter new setting then YES For LCD Press NO Ch...

Страница 34: ...larm 08 As Option 31 D1 Output Mode For LCD use YES key to move to desired channel and the NO key to change the setting for the selected channel 105 Digi D3 PA Term Mode Panic 07 As Option 31 D1 Outpu...

Страница 35: ...0 90 Minutes in ten minute increments LED 01 10 Minutes 02 20 Minutes 03 30 Minutes 04 40 Minutes 05 50 Minutes 06 60 Minutes 07 70 Minutes 08 80 Minutes 09 90 Minutes 130 FWT Mode Off 00 00 Off 01 Al...

Страница 36: ...Keyswitch Keypad Alert 1 Keys Keypad Alert 2 Keys Number of Keypads Multi Keypad Option Keyswitch Type Keypad Backlight Mode GARDTEC 800 Series Programming Part Test Chime are available on all models...

Страница 37: ...D Expander 1 O P3 3 For LED Expander 1 O P4 4 For LED Expander 2 O P1 5 For LED Expander 2 O P2 6 For LED Expander 2 O P3 7 For LED Expander 2 O P4 8 For LED Expander 3 O P1 9 For LED Expander 3 O P2...

Страница 38: ...c Zone Expander Card 10mA 12V d c Max 8 Per System Output Expander Card 40mA 12V d c Max 4 Per System Digigard Communicator 15mA 12V d c ProDigi Communicator 80mA 12V d c Gardtec 840 Modem 80mA 12V d...

Страница 39: ...s Loop Ohm V Sensor Part Info 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 91 92 GARDTEC 800 Series ords Recor...

Страница 40: ...r use with Gardtec Remote use this option To effect a reset of the factory defaults 1 Remove all power from the system for at least ten seconds 2 Apply power to the control panel mains power the displ...

Страница 41: ...ype Point ID or Mod PID for the Modem If using an LED type keypad to select Point ID With the display showing E press 34 followed by YES Then press NO 03 or 04 for Modem followed by YES It should be n...

Страница 42: ...he Tone Test Time option Miscellaneous GARDTEC 800 Series ve been added with the implementation of Point ID these are how Alarm Abort along with the time and date whilst the LED ow Test Call Sent alon...

Страница 43: ...ingdom Tel 01706 510000 Fax 01706 510100 nal Tel 44 1706 510000 Fax 44 1706 510100 ternet http www gardiner technology com e mail sales gardiner technology com Technical Support 01706 510200 Technical...

Отзывы: