CENTRIC User Guide, rel. 3.4
Register
Variable name
GET Values
Remarks
316
4x0316 Module 15 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
317
4x0317 Module 16 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
318
4x0318 Module 17 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
319
4x0319 Module 18 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
320
4x0320 Module 19 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
321
4x0321 Module 20 Alarm
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module configuration
322
4x0322 Alarm In More Than One
Module
0: Alarm off
1: Alarm on
323
4x0323 Static Switch Warning Or Alarm 0: Alarm off
1: Alarm on
324
4x0324 Static Switch Warning Or Alarm 0: Alarm off
1: Alarm on
325
4x0325 Over Temperature
0: Alarm off
1: Alarm on
326
4x0326 No AC Output To Load
0: Alarm off
1: Alarm on
327
4x0327 DC Voltage High
0: Alarm off
1: Alarm on
328
4x0328 DC Voltage Low
0: Alarm off
1: Alarm on
329
4x0329 End Of Battery Backup
0: Alarm off
1: Alarm on