7.2.4
Setup > STATIC SWITCH
Figure 22: "Setup > Static Switch" options
7.2.4.1
SETUP > ST.SW. > CALIBRATE BYPASS VOLTAGE
For calibration of the bypass voltage reading, by phase.
7.2.4.2
SETUP > ST.SW. > CALIBRATE INVERTER VOLTAGE
For calibration of the inverter voltage reading, by phase.
7.2.4.3
SETUP > ST.SW. > CALIBRATE OUTPUT VOLTAGE
For calibration of the ac output voltage reading, by phase.
7.2.4.4
SETUP > ST.SW. > CALIBRATE OUTPUT CURRENT
For calibration of the ac output current reading, by phase.
Note:
•
Static switch output current calibration should be performed only if necessary, not casually.
•
Static switch output current calibration should be performed only under conditions where the
system input and output current are stable and not subject to fluctuation.
•
Calibration is best performed when the system is under relatively high load (70+ %).