CENTRIC User Guide, rel. 3.4
49
Register
Variable name
GET Values
Remarks
330
4x0330 Low Battery Voltage
0: Alarm off
1: Alarm on
331
4x0331 Emergency Power Off Is Active 0: Alarm off
1: Alarm on
332
4x0332 Batteries Failed Last Test
0: Alarm off
1: Alarm on
333
4x0333 AC Input Voltage Low
0: Alarm off
1: Alarm on
334
4x0334 AC Input Voltage High
0: Alarm off
1: Alarm on
335
4x0335 AC Input Failure
0: Alarm off
1: Alarm on
336
4x0336 No Output Current On Modules 0: Alarm off
1: Alarm on
337
4x0337 Overload
0: Alarm off
1: Alarm on
338
4x0338 Battery Test In Progress
0: Alarm off
1: Alarm on
339
4x0339 Auxiliary Input Volt-Free
Contact 1 Fault
0: Alarm off
1: Alarm on
340
4x0340 Auxiliary Input Volt-Free
Contact 2 Fault
0: Alarm off
1: Alarm on
341
4x0341 Auxiliary Input Volt-Free
Contact 3 Fault
0: Alarm off
1: Alarm on
342
4x0342 Auxiliary Input Volt-Free
Contact 4 Fault
0: Alarm off
1: Alarm on
343
4x0343 Auxiliary Input Volt-Free
Contact 5 Fault
0: Alarm off
1: Alarm on