Heat Ex. Liquid Outlet Thermistor Error
Outdoor unit Main PCB
Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
02-25
7.7
5
9.7
12.4
16.1
20.9
27.5
49.2
Resistance value (k )
5
-
0
-10
-20
92.3
-30
Temperature
(°C )
10
15
0.9
1.3
1.8
2.6
4.0
Resistance value (k )
70
0.7
80
0.5
90
0
3
0
4
0
5
0
6
6.1
20
Temperature
(°C )
BROWN
BROWN
BLUE
BLUE
Thermistor
(Discharge pipe)
Thermistor
(Heat exchanger)
Thermistor
(Outdoor temp.)
Thermistor
(Compressor temp.)
3
2
1
3
2
1
3
2
1
3
2
1
CN62
BLACK
BLACK
3
2
1
3
2
1
CN65
BROWN
BROWN
3
2
1
3
2
1
CN63
CN64
Indicate or Display:
Indoor Unit :
Operation lamp: 7 times Flash,
Timer lamp : 3 times Flash
ERROR CODE : [E : 73]
Wired Remote Controller :
AMP Air Conditioning
www.ampair.co.uk | [email protected]