8-1-2. Install the terminal block
(1) Attach the terminal block to the indoor unit firmly with 1 screw.
(2) Place the wiring as per the figure.
(Front view)
Terminal block (with wire)
(Rightside view)
Place wire under the tab.
Indoor unit main PCB
Screw
Place the wires from the terminal
block under the other wires.
(3) Connect the wires from the terminal block to the indoor unit main PCB by inserting to connector (CN12).
(4) Change the DIP switch setting as shown in the following photograph.
Connector (CN12)
(Indoor unit main PCB)
Terminal block
wires
2WIRE/3WIRE
CAUTION
•
Be careful not to damage the parts on the board. Otherwise, it will cause malfunction.
•
Ensure that the connector is properly inserted. Otherwise, it may result in erroneous operation.