1-3. Error code table (Indoor unit and wired remote controller)
The operation, timer, and economy indicators operate according to the error contents.
For confirmation of the error contents, refer the flashing pattern as follows.
Error contents
Indoor unit display
Wired
remote
controller
display
Operation [ ]
(Green)
Timer [ ]
(Orange)
Economy [ ]
(Green)
E: 11. Serial communication error (Serial
reverse transfer error) (Outdoor unit)
1 times
1 times
Continuous
11
E: 11. Serial communication error (Serial
forward transfer error) (Indoor unit)
1 times
1 times
Continuous
11
E: 18. External communication error
between indoor unit and WLAN adapter
1 times
8 times
Continuous
18
1 times
8 times
Continuous
18
E: 18. Wireless LAN adapter non-energized
1 times
8 times
Continuous
18
E: 32. Indoor unit main PCB error (Indoor
unit)
3 times
2 times
Continuous
32
E: 35. MANUAL AUTO button error (Indoor
unit)
3 times
5 times
Continuous
35
E: 41. Room temperature sensor error
(Indoor unit)
4 times
1 times
Continuous
41
E: 42. Indoor unit heat exchanger sensor
error (Indoor unit)
4 times
2 times
Continuous
42
E: 51. Indoor unit fan motor error (Indoor
unit)
5 times
1 times
Continuous
51
E: 62. Outdoor unit main PCB error
(Outdoor unit)
6 times
2 times
Continuous
62
E: 64. PFC circuit error (Outdoor unit)
6 times
4 times
Continuous
64
E: 65. IPM error (Outdoor unit)
6 times
5 times
Continuous
65
E: 71. Discharge thermistor error (Outdoor
unit)
7 times
1 times
Continuous
71
E: 73. Outdoor unit heat exchanger
thermistor error (Outdoor unit)
7 times
3 times
Continuous
73
E: 74. Outdoor temperature thermistor error
(Outdoor unit)
7 times
4 times
Continuous
74
E: 84. Current sensor error (Outdoor unit)
8 times
4 times
Continuous
84
E: 94. Trip detection (Outdoor unit)
9 times
4 times
Continuous
94
E: 95. Compressor motor control error
(Outdoor unit)
9 times
5 times
Continuous
95
E: 97. Outdoor unit fan motor error
(Outdoor unit)
9 times
7 times
Continuous
97
E: 99. 4-way valve error (Outdoor unit)
9 times
9 times
Continuous
99
E: A1. Discharge temperature error
(Outdoor unit)
10 times
1 times
Continuous
A1
1-3. Error code table (Indoor unit and wired remote controller)
- (03-2) -
1. Error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...