2-10. E: 65. IPM error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
6 time flash
Timer indicator
5 time flash
Economy indicator
Continuous flash
Error code
E: 65
Detective actuator
Outdoor unit
Main PCB
1. When more than normal operating current to IPM in
main PCB flows, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Outdoor fan operation failure
Outdoor heat exchanger clogged
Compressor failure
Main PCB failure
Check point 1. Check connections of outdoor unit electrical components
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 2. Check outdoor fan and heat exchanger
•
Is there anything obstructing the air distribution circuit?
•
Is there any clogging of outdoor heat exchanger?
•
Is the fan rotating by hand when operation is off?
→ If the fan motor is locked, replace it.
↓
Check point 3. Check outdoor fan
Check outdoor fan motor. (Refer to
"E: 97. Outdoor unit fan motor error (Outdoor unit)"
23.)
→ If the fan motor is failure, replace it.
↓
2-10. E: 65. IPM error (Outdoor unit)
- (03-15) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...