Model: AOHG12KPCA
Fan speed is defined by outdoor temperature and rotation number of the compressor.
•
Outside air temperature zone selection
21
°C
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
12
°C
2
°C
19
°C
10
°C
0
°C
Unit: rpm
Fan step
Cooling
Heating
Dry
Cooling or dry at low outdoor temp.
Y zone
Y zone
Z zone
F zone
G zone
S-HIGH2
—
1,020
—
—
—
—
S-HIGH1
950
1,020
—
—
—
—
HIGH
950
1,020
—
—
—
—
10
—
790
—
—
—
—
9
950
790
950
950
950
950
8
900
790
900
900
350
300
7
900
790
900
900
350
300
6
900
790
900
560
350
300
5
900
730
900
420
320
230
4
800
630
800
350
290
230
3
680
530
680
350
270
230
2
580
470
580
350
270
230
1
540
470
540
350
250
230
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
rotation number of compressor.
Fan speed after defrost control: 1,020 rpm
3-2. Outdoor fan control
- (04-13) -
3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...