8-7. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode
Cooling/Dry
Trigger condition
-15°C
Release condition
-10°C
8-8. High temperature and high pressure release control
The compressor is controlled as follows.
¢
Models: AOHG07KPCA, AOHG09KPCA, and AOHG12KPCA
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB:
63°C
BC:
55°C
CD:
53°C
DE:
50°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The rotation number of compressor is decreased.
-25 rps/120 sec.
Zone C
-3 rps/60 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-7. Low outdoor temperature protection
- (04-29) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS