1-5. Limitation of compressor rotation number by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name
Outdoor temperature zone
Limitation of compressor
rotation number
AOHG07KPCA
AOHG09KPCA
A zone
42 rps
B zone
42 rps
C zone
33 rps
D zone
28 rps
E zone
16 rps
F zone
21 rps
AOHG12KPCA
A zone
38 rps
B zone
38 rps
C zone
33 rps
D zone
28 rps
E zone
16 rps
F zone
21 rps
•
Heating mode
F zone
19°C
E zone
5°C
D zone
0°C
C zone
B zone
A zone
-15°C
-25°C
Model name
Outdoor temperature zone
Limitation of compressor
rotation number
AOHG07KPCA
AOHG09KPCA
AOHG12KPCA
A zone
43 rps
B zone
43 rps
C zone
30 rps
D zone
18 rps
E zone
16 rps
F zone
16 rps
1-5. Limitation of compressor rotation number by outdoor temperature
- (04-5) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General ASHG07KPCE
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Страница 34: ......
Страница 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Страница 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...