FUNCTION DETAILS
Function Function
number Setting number Default
Details
Filter
indicator
interval
66
00
Default
Adjust the filter cleaning interval notifi cation. If the
notification is too early, change to setting 01. If the
notification is too late, change to setting 02.
06
Longer
02
Shorter
Filter
indicator
action
63
00
Enable
Enable or disable the fi lter
indicator. Setting 02 is for use
with a central remote control.
06
Disable
02
Display
only on
central
remote
control
Ceiling
airflow
20
00
Default
Regulate the airfl ow according to the needs of the
installation location. When set to 01, the air flow will be
stronger.
06
High
Ceiling
Vertical
airflow
direction
23
00
Default
Adjust the vertical airflow direction. All airflow direction
louvers are adjusted together.
(Cassette type only)
06
Raise
Horizontal
swing
airflow
direction
24
00
Default
Adjust the horizontal swing airflow direction.
(For horizontal swing equipped models)
06
Left half
02
Right half
Cool
air tem-
perature
trigger
30
00
Default
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
06
Adjust (1)
02
Adjust (2)
Heat
air tem-
perature
trigger
36
00
Default
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the
trigger temperature by 4 degrees C, use setting 02. To raise
the trigger temperature, use setting 03.
06
Adjust (1)
02
Adjust (2)
03
Adjust (3)
Auto
restart
40
00
Enable
Enable or disable automatic system restart after a power
outage.
06
Disable
External
control
46
00
Start/Stop
Allow an external controller to start or stop the system, or to
perform an emergency stop.
* If an emergency stop is performed from an external
controller, same refrigerant system will be disabled.
06
Emergen-
cy stop
Error
report
target
47
00
All
Change the target for reporting errors. Errors can either be
reported in all locations, or only on the wired remote.
06
Display
only on
central
remote
control
- (06 - 117) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...