REFRIGERANT CIRCUIT ADDRESS SETTING
z
Note : The refrigerant circuit address can also be set evenwhile above indoor unit address display.
(14) Press the “FAN” button to select the
function number.
(15) Press the "
p
" or the "
q
" button to adjust
function number
02.
(16) Press the “FAN” button to access the
address data
setting mode. The address
data will flash once this button is pressed.
(17) Press the "
p
" or the "
q
" buttons to
adjust the address data
. The refrigerant
circuit address range is between 00 and 99.
Each time the "MODE" button is pressed,
it switches between 1 unit and 10 units
positions.
(18) Press the “START/STOP” button once to
send the information. A beeping noise will
be heard if the command is accepted.
In the following cases the setting signal is not read
and a buzzer sounds.
The setting of the rotary switch on the PCB is not
"00" : Pi Pi Pi Pi Pi
(19) Indoor unit will display the refrigerant
circuit address data number on "TIMER
"(ORANGE) and "FILTER "(RED) light.
ADDRESS 0 setting will not indicate TIMER LAMP and
FILTER LAMP.
ADDRESS display will automatically switched from
indoor unit address to refrigerant circuit address.
Confirmation of address setting
z
(20) Press the “TIMER set (+)” button.
SET "02"
Range
00 - 99
: UP
: DOWN
Change digit
(Example) ADDRESS : 25
OPERATION LAMP
(GREEN)
TIMER LAMP
(ORANGE)
FILTER LAMP
(RED)
0.5sec ON / 0.5sec OFF
1sec ON / 1sec OFF
5 times
2 times
1 - 10 sec
1 - 10 sec
0.5sec ON / 0.5sec OFF
OPERATION
(GREEN)
TIMER
(ORANGE)
1 sec ON
1 sec OFF
Flashing times of
address numbers
(10 digit)
FILTER
(RED)
Flashing times of
address numbers
(1 digit)
Pi Pi
Pi PiPiPi
PiPi
CORRECT : Pi PiPiPiPiPi
PiPi
WRONG: Pi (3 sec)
Function number
Address data
“TIMER set (+)”
- (06 - 82) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...