553535 SIGNAL AMPLIFIER
MODEL : UTY 5 VSGX
If the total length of transmission line exceeds 500m, or the number of units exceeds 64 units,
Signal Amplifier will be necessary to use.
FEATURES
To prevent the drop of signal level by taking distance of length or quantity of unit in VRF
network with installing signal amplifier, signal level can be recovered.
Transmission line length can be extended up to 3600m with multiple
●
signal amplifier.
Up to 8 Signal Amplifier can be installed in a VRF system.
●
SYSTEM DIAGRAM
Each network segment must be within
Total wiring length of transmission line : 500m
●
A number of units : 64
●
The number of control unit [Group Remote Controller Touch Panel Controller, System
●
Controller and Network Convertor] : Max 2
The number of terminal resistor : 1
●
Note:
22AWG Level 4 cable with shielded(National Electrical Manufacturers Association (NEMA) ) **differs from
●
the Category 4 specification proposed by the Electronic Industries Association/Telecommunication Industry
Association (EIA/TIA)**
Unit means indoor unit, outdoor unit, signal amplifier, network convertor, touch panel controller, system
●
controller and so on.
1
1
2
3
4
1
6
2
3
1
2
3
4
5
4
62
62
64
64
10
18
63
63
11
12
13
14
15
16
17
2
3
4
5
6
7
8
9
Network
segment 5
Signal
Amplifier
Signal
Amplifier
Transmission line : within 500m
Refrigerant system 4
Refrigerant system 3
Refrigerant system 2
Refrigerant system 1
master
master
master
master
slave1
slave1
slave1
slave2
slave2
64units
64units
2 control units
Signal
Amplifier
Network
segment 2
Network
segment 3
Network
segment 4
- (05 - 71) -
C
O
N
TRO
L
SY
ST
EM
C
O
N
TRO
L
SY
ST
EM
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...