When “11” appears on the LED105, hold down the ENTER button (SW109) for at least 3
5)
seconds.(Unless it is held down for at least 3 seconds, the selection will not be confirmed.)
When the Automatic Address Setting function is activated, the display changes to “run.”
When automatic address setting is completed, the number of indoor units of which automatic
6)
address setting succeeded is displayed on the LED105, and the number of indoor units of
which automatic address setting failed is displayed on the LED104.
Ex.) When 25 indoor units are connected, and the automatic setting of the addresses of all
indoor units ended normally
Ex.) When 25 indoor units are connected, and the automatic setting of the addresses of
three indoor units failed
If automatic address setting failed, make sure that all of the rotary switches SW6 to SW9 on
the PCBs of the failed indoor units are positioned at 0 and that wiring and power supply are
correct, and then perform automatic address setting again.
When the ENTER button (SW109) is pressed, it takes about 30 seconds for end processing.
7)
During that time, the LED display blinks.
Setting is complete when the LED display goes off.
LED105
LED104
LED105
LED104
(Setting completed)
LED105: The number of indoor
units of which automatic
address setting succeeded
LED104: The number of indoor
units of which automatic
address setting failed
LED105
LED104
LED105
LED104
LED105: The number of indoor
units of which automatic
address setting succeeded
LED104: The number of indoor
units of which automatic
address setting failed
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
LED105
LED104
- (06 - 98) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...