EXTERNAL INPUT & OUTPUT
6676
667666 OUTDOOR UNIT
INPUT (Master unit only)
Setting to low noise mode, cooling priority/heating priority selection, outdoor unit operation
peak control setting and emergency stop are possible from the outside.
Connector
Input signal
Status
CN131 (Yellow)
OFF
Normal operation
ON
Low noise mode operation
CN132 (Green)
*1
OFF
Cooling priority
ON
Heating priority
CN133 (White)
OFF
Normal operation
ON
Outdoor unit operation peak control
CN134 (Red)
OFF
Normal operation
ON
Forced stop or Emergency stop operation *2, *3
A twisted pair cable (22AWG) shoud be used. Maximum length of cable is 150m.
1 2
1 2
1 2
1 2
CN131
(Yellow)
Input1
connected unit connected unit connected unit connected unit
Input2
Input3
Input4
CN132
(Green)
CN133
(White)
CN134
(Red)
P.C.B
Note :
*1: The "external input priority mode" must be set by pressing push button on PC board of outdoor
unit.
*2: Forced stop or Emergency stop pattern can be selected by outdoor unit PC board push button.
*3: The emergency stop function mounted in the V-II does not guarantee the regulations of each
country. For this reason, sufficient checking is necessary regarding use.
Especially, since the fact that the equipment may not be emergency-stopped in the case of
breaking of the wiring to the external input terminals and communication line, communication
error due to noise, VRF external input circuit trouble, etc. must be considered, the provision of
double measures that add direct interruption of the power supply by switch, etc. is recommended
as a precaution.
Note :
The length regulations of the cable are as shown in the following figures.
1
2
connected unit
Max. Length = L
cable
P.C.B
Type
L (m)
Type
L (m)
Input /
Output
Input /
Output
Outdoor unit
150 / 150
Floor/Ceiling
25 / 25
Compact Cassette
Ceiling
Cassette
Compact Wall
Mounted
Compact Duct
25 / 25
Low Static Duct
Wall Mounted
Duct
Touch Panel
Controller
High Static Duct
- (06 - 142) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...