665656 WIRED REMOTE CONTROLLER ADDRESS SETTING
Indoor unit addresses and refrigerant circuit addresses can be set up using wired remote
●
controllers.
This function allows setting the addresses of all indoor units to which a wired remote
●
controller is being connected.
This function cannot be used to set up remote controller addresses.
●
Be sure to set them up using the rotary switches on the PCB of each indoor unit. (Refer to
6-5-3.)
PREPARATION
Make sure that all indoor unit address switches (IU AD x10, IU AD x1) and refrigerant
1)
circuit address switches (REF AD x10, REF AD x1) on the PCB of each indoor unit are
set at 0 (factory setting).
If any of the switches is positioned at a value other than 0, this function will not
●
activate.
The layout of the switches differs depending on the type of the indoor unit. (Refer to
●
6-6-2.)
Turn on the power to the indoor unit.
3)
By turning on the power indoor units initializes EEV, so make sure the piping air-
●
tight test and vacuuming have been conducted before turning on the power.
Also check again to make sure no wiring mistakes were made before turning on
●
the power.
Breaker ON
20A
Indoor
units
Indoor
units
If multiple indoor units are connected to a single wired remote controller, make sure
2
)
to manually set up the remote controller address (RC AD) on the PCBs of the indoor
units. (Refer to 6-5-3.)
Ex.) When four indoor units are connected
SW1 SW2
SW3 SW4 SW5
SW6
SW7
SW8
SW9
SW10
Rotary switch
(type A)
Check the position “0”
(Factory setting)
IU AD x10
IU AD x1
REF AD x10
REF AD x1
0
1
2
3
Indoor unit
Indoor unit
Indoor unit
Indoor unit
RC AD
RC AD
RC AD
RC AD
Wired
remote
controller
- (06 - 85) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Содержание AIRSTAGE V-II
Страница 10: ...1 GENERAL INFORMATION ...
Страница 32: ...2 MODEL SELECTION ...
Страница 207: ...3 OUTDOOR UNITS ...
Страница 251: ...SOUND LEVEL CHECK POINT Microphone 1 m 1 m 03 44 OUTDOOR UNITS OUTDOOR UNITS ...
Страница 265: ...4 INDOOR UNITS ...
Страница 308: ... Unit mm INSTALLATION PLACE 50 or more 90 or more 60 or more 1800 or more 1500 or more 04 43 INDOOR UNITS INDOOR UNITS ...
Страница 310: ... Unit mm INSTALLATION PLACE 60 or more 200 or more 50 or more 1500 or more 2300 or more 04 45 INDOOR UNITS INDOOR UNITS ...
Страница 312: ...4 5 2 CASSETTE TYPE MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 04 47 INDOOR UNITS INDOOR UNITS ...
Страница 313: ...4 5 3 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 04 48 INDOOR UNITS INDOOR UNITS ...
Страница 314: ...4 5 4 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24 MODELS ARXB30 ARXB36 04 49 INDOOR UNITS INDOOR UNITS ...
Страница 315: ...MODEL ARXB45 04 50 INDOOR UNITS INDOOR UNITS ...
Страница 316: ...4 5 5 DUCT TYPE MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 04 51 INDOOR UNITS INDOOR UNITS ...
Страница 317: ...4 5 6 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 04 52 INDOOR UNITS INDOOR UNITS ...
Страница 318: ...4 5 7 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 04 53 INDOOR UNITS INDOOR UNITS ...
Страница 319: ...4 5 8 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 04 54 INDOOR UNITS INDOOR UNITS ...
Страница 320: ...4 5 9 COMPACT WALL MOUNTED TYPE EEV internal model MODELS AS A07 AS A09 AS A12 AS A14 04 55 INDOOR UNITS INDOOR UNITS ...
Страница 321: ...4 5 10 COMPACT WALL MOUNTED TYPE EEV external model MODELS AS E07 AS E09 AS E12 AS E14 04 56 INDOOR UNITS INDOOR UNITS ...
Страница 322: ...4 5 11 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 04 57 INDOOR UNITS INDOOR UNITS ...
Страница 388: ...5 CONTROL SYSTEM ...
Страница 472: ...6 SYSTEM DESIGN ...
Страница 694: ...7 OPTIONAL PARTS ...