2. Troubleshooting with error code
2-1. E: 11. Serial communication error (Serial reverse transfer
error) (Outdoor unit)
Indicator
→ired remote
controller
Error code
E: 11
Detective actuator Outdoor unit
Main PCB
→hen the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
than 15 seconds during normal operation.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Outdoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
If there is an abnormal condition, correct it by referring to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at
outdoor unit terminal L — N.
+
-
2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)
- (03-3) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...