2-26. E: 95. Compressor motor control error (Outdoor unit)
Indicator
→ired remote
controller
Error code
E: 95
Detective actuator Outdoor unit
Main PCB
1. →hen running the compressor, if the detected rotor
location is out of phase with actual rotor location
more than 90°, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Main PCB failure
Compressor failure
Check point 1. Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace compres-
sor.
Check point 2. Check connection of around the compressor components
For compressor terminal, main PCB
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open. (Refer to inverter compressor in
44.)
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 3. Replace main PCB
If Check point 1, 2 do not improve the symptom, change main PCB.
Check point 4. Replace compressor
If Check point 3 do not improve the symptom, change compressor.
End
2-26. E: 95. Compressor motor control error (Outdoor unit)
- (03-31) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...