2-28. E: 99. 4-way valve error (Outdoor unit)
Indicator
→ired remote
controller
Error code
E: 99
Detective actuator
Indoor unit
main PCB
→hen the indoor heat exchanger temperature is
compared with the room temperature, and either
following condition is detected continuously two times,
the compressor stops.
Indoor heat exchanger temp. - Room temp. > 20 °F
(10 °C) (Cooling or Dry operation)
Indoor heat exchanger temp. - Room temp. < -20 °F
(-10 °C) (Heating operation)
If the same operation is repeated 5 times, the
compressor stops permanently.
Heat exchanger temperature
thermistor
Room temperature thermistor
4-way valve
Forecast of cause
Connector connection failure
Thermistor failure
Coil failure
4-way valve failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if thermistor cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check each thermistor
•
Isn’t it fallen off the holder?
•
Is there a cable pinched?
Check characteristics of room thermistor and indoor unit heat exchanger thermistor.
For the thermistor resistance value, refer to
"Thermistor resistance values"
If defective, replace the thermistor.
2-28. E: 99. 4-way valve error (Outdoor unit)
- (03-33) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...