1-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
¢
Setting procedure by using remote controller
Remote controller is not attached for this product. For details of the installing remote controller, refer
to following information.
• Overview information: Operating manual of the remote controller
• Setting procedure: Installation manual of the remote controller
¢
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
Function setting list
Function no.
Functions
1)
11
Filter sign
2)
20
Ceiling height
3)
22
Outlet directions
4)
30/31
Room temperature control for indoor unit sensor
5)
35/36
Room temperature control for wired remote controller sensor
6)
40
Auto restart
7)
42
Room temperature sensor switching
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
11)
49
Indoor unit fan control for energy saving for cooling
12)
60
Switching functions for external output terminal
13)
61
Control switching of external heaters
14)
62
Operating temperature switching of external heaters
15)
66
Outdoor temperature zone boundary temperature A
16)
67
Outdoor temperature zone boundary temperature B
17)
71
Standby time for auxiliary equipment operation
18)
72
Heat pump backup setting
19)
73
Emergency heat
20)
75
External heater use in defrosting
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (2,500 hours)
01
Long interval (4,400 hours)
02
Short interval (1,250 hours)
03
No indication
♦
1-2. Function settings by using remote controller
- (05-2) -
1. Function settings
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...