2-20. E: 65. IPM error (Outdoor unit)
Detective actuator Outdoor unit
Main PCB
1. →hen more than normal operating current to IPM in
main PCB flows, the compressor stops.
2. After the compressor restarts, if the same operation
is repeated within 40 seconds, the compressor
stops again.
3. If 1. and 2. repeats 5 times, the compressor stops
permanently.
Compressor
Forecast of cause
Defective connection of electric components
Outdoor fan operation failure
Outdoor heat exchanger clogged
Compressor failure
Main PCB failure
Check point 1. Check connections of outdoor unit electrical components
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check outdoor fan and heat exchanger
•
Is there anything obstructing the air distribution circuit?
•
Is there any clogging of outdoor heat exchanger?
•
Is the fan rotating by hand when operation is off?
If the fan motor is locked, replace it.
Check point 3. Check outdoor fan
Check outdoor fan motor. (Refer to
"E: 97. Outdoor unit fan motor error (Outdoor unit)"
32.)
If the fan motor is failure, replace it.
2-20. E: 65. IPM error (Outdoor unit)
- (03-24) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...