During heating mode or fan mode and when operation is stopped
•
Triggering condition
Drain pump is turned on at the same time that the float switch is turned on.
•
Operation details
→hen the float switch turns on continuously for 3 minutes, "failure indication" operates. There-
after, even if the float switch turns off, the "failure indication" is not released. (It is necessary to
turn off power for release it.)
3 minutes
On
Off
On
Off
Float switch
Drain pump
•
Release condition
Drain pump operates continuously for 3 minutes after the float switch is turned off and then
drain pump is turned off.
7-9. Prevention to restart for 3 minutes (3 minutes st)
→hen the compressor fails to start for the number of times below, it does not enter operation status
for 3 minutes.
Retry number
50
Retry set number
3
→hen the compressor fails to start in the retry set number above, the compressor is stopped.
7-10. 4-way valve control
• If heating mode is selected at the compressor start, 4-way valve is energized for heating.
• →hen the air conditioner is switched between cooling and heating mode, compressor is stopped,
and the 4-way valve is switched when the 140 seconds passes and the compressor is started.
7-8. Drain pump control
- (04-29) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...