Available Sensor ID
Sensor ID
Item
Unit
Remarks
00
158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
162
External output command by remote
controller (External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
01: Outdoor unit
01
000
Outdoor temp.
01: °F or °C
01
001
Discharge temp.
01: °F or °C
01
003
Heat exchanger middle temp.
01: °F or °C
01
004
Heat exchanger outlet temp.
01: °F or °C
01
007
Compressor temp.
01: °F or °C
01
050
Fan 1 rotation number
03: rpm
01
055
Compressor rotation number
04: rps
01
060
Expansion valve (Upstream during
heating)
05: pls
01
080
4-way valve output status
07: Cooling/
Heating
0: Cooling, 1: Heating
01
100
Operating current
09: A
01
110
Outdoor unit total power-on hours
11: h
01
111
Compressor total heating operation
hours
11: h
01
112
Compressor total cooling operation
hours
11: h
01
113
Compressor total operation hours
11: h
01
114
Outdoor unit fan 1 total operation
hours
11: h
7-11. Unit status monitoring and the detected value indication
- (04-31) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Содержание ACUH09LUAS1
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Страница 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Страница 48: ......
Страница 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Страница 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...