![Fuji Electric Frenic-Sce Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/fuji-electric/frenic-sce/frenic-sce_instruction-manual_2341867008.webp)
1-3
Operation
• Be sure to mount the front cover before turning the power ON. Do not remove the cover when the inverter
power is ON.
Otherwise, an electric shock could occur.
• Do not operate switches with wet hands.
Doing so could cause electric shock.
• If the auto-reset function has been selected, the inverter may automatically restart and drive the motor
depending on the cause of tripping. Design the machinery or equipment so that human safety is ensured at
the time of restarting.
Otherwise, an accident could occur.
• If the stall prevention function (current limiter), automatic deceleration (anti-regenerative control), or
overload prevention control has been selected, the inverter may operate with acceleration/deceleration or
frequency different from the commanded ones. Design the machine so that safety is ensured even in such
cases.
• The
key on the keypad is effective only when the keypad operation is enabled with function code F02 (=
0, 2 or 3). When the keypad operation is disabled, prepare an emergency stop switch separately for safe
operations.
Switching the run command source from keypad (local) to external equipment (remote) by turning ON the
"Enable communications link" command
LE
disables the
key. To enable the
key for an emergency
stop, select the STOP key priority with function code H96 (= 1 or 3).
• If any of the protective functions have been activated, first remove the cause. Then, after checking that the
all run commands are set to OFF, release the alarm. If the alarm is released while any run commands are set
to ON, the inverter may supply the power to the motor, running the motor.
Otherwise, an accident could occur.
• If you enable the "Restart mode after momentary power failure" (Function code F14 = 3 to 5), then the
inverter automatically restarts running the motor when the power is recovered.
Design the machinery or equipment so that human safety is ensured after restarting.
• If the user configures the function codes wrongly without completely understanding this User's Manual, the
motor may rotate with a torque or at a speed not permitted for the machine.
• Starting auto-tuning involves motor rotation. Sufficiently check that motor rotation brings no danger
beforehand.
An accident or injuries could occur.
• Even if the inverter has interrupted power to the motor, if the voltage is applied to the main circuit input
terminals L1/R, L2/S, L3/T, L1/L and L2/N, voltage may be output to inverter output terminals U, V, and W.
• Even if the motor is stopped due to DC braking or preliminary excitation, voltage is output to inverter output
terminals U, V, and W.
An electric shock may occur.
• The inverter can easily accept high-speed operation. When changing the speed setting, carefully check the
specifications of motors or equipment beforehand.
Otherwise, injuries could occur.
• Do not touch the heat sink and braking resistor because they become very hot.
Doing so could cause burns.
• The DC brake function of the inverter does not provide any holding mechanism.
Injuries could occur.
• Ensure safety before modifying the function code settings.
Run commands (e.g., "Run forward"
FWD
), stop commands (e.g., "Coast to a stop"
BX
), and frequency
change commands can be assigned to digital input terminals. Depending upon the assignment states of
those terminals, modifying the function code setting may cause a sudden motor start or an abrupt change in
speed.
• When the inverter is controlled with the digital input signals, switching run or frequency command sources
with the related terminal commands (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
, and
LE
) may cause
a sudden motor start or an abrupt change in speed.
• Ensure safety before modifying customizable logic related function code settings (U codes and related
function codes) or turning ON the "Cancel customizable logic" terminal command
CLC
. Depending upon the
settings, such modification or cancellation of the customizable logic may change the operation sequence to
cause a sudden motor start or an unexpected motor operation.
An accident or injuries could occur.
Содержание Frenic-Sce
Страница 10: ......