5-7
F07, F08
Acceleration time1, Deceleration time1
(Refer to F37)
Acceleration time sets the time taken by the output frequency to reach the maximum output frequency from 0Hz,
and deceleration time sets the time taken by the output frequency to reach 0Hz from the maximum frequency.
• Data setting range: 0.00 to 6000 (s)
For V/f control
F09
Torque boost 1
(Refer to F37)
For details of torque boost 1 setting, refer to the section of function code F37.
F10 to F12
Electronic thermal overload Protection for motor 1 (Select motor characteristics,
Thermal time constant)
In order to detect overload of motor (electronic thermal function by inverter output current), set temperature
characteristics of motor: Select motor characteristics (F10), thermal time constant (F12), and overload detection
level (F11).
When overload of motor is detected, inverter is turned off, protecting the motor with motor overload alarm
0l1
.
Improper setting of the electronic thermal function may result in a failure to protect the motor from
burning.
Temperature characteristics of motor is used for motor overload early warning "OL" as well. Even if only
overload early warning is used, it is necessary to set temperature characteristics of the motor (F10, F12).
(
Function code E34)
For disabling motor overload alarm, set F11 = 0.00 (Disable).
For PTC thermistor built-in motor, by connecting PTC thermistor to terminal [C1], it is possible to protect
the motor. Refer to H26 to find the details.
Starting frequency 1
Acceleration time 1
Deceleration
time 1
Stop frequency
Actual
deceleration time
Actual
acceleration time
Maximum
output
frequency