6-5
Continuation of Table 6.3-1
Alarm code
Alarm code name
Heavy
failure
object
Light
alarm
selectable
Retry
object
Alarm subcode*
Alarm subcode name
0c1
Instantaneous overcurrent
Y
-
Y
1 to 5001
For manufacturer
0c2
0c3
0h1
Cooling fin overheat
Y
Y
Y
6
Detection of fan stop
Other than above
For manufacturer
0h2
External alarm
Y
Y
-
-
-
0h3
Inverter internal overheat
Y
Y
Y
0
Internal air overheat
1
Charging resistor overheat
Other than above
For manufacturer
0h4
Motor protection (PTC
thermistor)
Y
-
Y
-
-
0h6
Charging resistor overheat
Y
Y
Y
-
-
0l1
Motor 1 overload
Y
Y
Y
-
-
0l2
Motor 2 overload
Y
Y
Y
-
-
0lu
Inverter overload
Y
-
Y
1
IGBT protection
2
Inverter overload
10
For manufacturer
0pl
Output phase-failure
detection
Y
-
-
1 to 10
For manufacturer
0s
Overspeed protection
Y
-
-
-
-
0u1
Overvoltage
Y
-
Y
1 to 12
For manufacturer
0u2
0u3
pbf
Charger circuit fault
(FRN0203E2
■
-4
or
above)
Y
-
-
1 to 2
For manufacturer
pg
PG wire break
Y
-
-
10 to 20
For manufacturer
cnT
Inverter life (Number of
startups)
-
Y
-
-
-
fal
Detect DC fan lock
-
Y
-
-
-
lif
Lifetime alarm
-
Y
-
-
-
0h
Cooling fin overheat early
warning
-
Y
-
-
-
0l
Overload early warning
-
Y
-
-
-
pid
PID alarm output
-
Y
-
-
-
pTc
PTC thermistor activated
-
Y
-
-
-
ref
Reference command loss
detected
-
Y
-
-
-
rTe
Machine life (Cumulative
motor running hours)
-
Y
-
-
-
uTl
Low torque detection
-
Y
-
-
-
NB)
• If a control power supply voltage drops to such a level that the operation of the inverter control circuit
cannot be maintained, all protective functions are automatically reset.
• By OFF
ON operation of
key or X terminal (assigned to RST), the protection stop state can be
released. In a state that an alarm cause is not removed, however, resetting operation is not effective.
• If two or more alarms are occurring, the resetting operation remains ineffective until all the alarm causes
are removed. Alarm factors not removed can be checked from the keypad.
• When assigned to light alarms, "30A/B/C" do not change.