Functional description of the slide switches is given in Table 2.2.8-1 "Functional Description of Various Switches."
Table 2.2.8-1 Functional Description of Slide Switches
Switch
symbol
Functional description
SW1
<Switch to change sink/source setting of digital input terminals>
• This switch determines the type of input (sink or source) to use for digital input terminals [X1] to [X5],
FWD, and REV.
SW2
<Switch to change the RS-485 communication terminating resistor (RS-485 communication port (on the
control PCB))>
• Move to the ON side when RS-485 communication is used and this inverter is connected to the
termination.
SW3
SW4
<Switch to change terminal [C1] input setting to current/voltage/PTC thermistor>
This switch changes the input type for terminal [C1].
Input type
SW3
SW4
E59
H26
Current input (factory default)
C1 side
AI side
0
0
Voltage input
V2 side
AI side
1
0
PTC thermistor input
C1 side
PTC side
0
1
SW5
<Switch to change terminal [FM] output setting to current/voltage/pulse>
This switch changes the output type for terminal [FM]. When operating this switch, also change function
code F29.
Output type
SW5
F29
Current output
FMI side
1 or 2
Voltage output (factory default)
FMV side
0
Pulse output
FMP side
3
SW6
<Switch to change the RS-485 communication terminating resistor (RS-485 communication port (on the
terminal board))>
FRN
E2
-
A, E, K, U
• Used for the RS-485/CANopen communication. Move the switch to the ON position when the inverter is
connected to the terminal. They cannot be used simultaneously.
FRN
E2
-
C
• Used for the RS-485 communication. Move the switch to the ON position when the inverter is connected
to the termination.
SW7
<Switch to change terminal [FM2] output setting to voltage/current> The terminal is used only on the
FRN
E2
-
C.
This switch changes the output type for terminal [FM2]. When operating this switch, also change function
code F32.
Output type
SW7
F32
Voltage output
FMV2 side
0
Current output
FMI2 side
1 or 2
SW8
<Switch to change terminal [FM2] output setting to general-purpose/
SRCF
>
This switch changes the output for terminal [Y2].
Output
SW8
General-purpose output
Y2 side
SRCF
output
SRCF side
Exercise caution as expected operation may not result if the setting above is not conducted accurately.