2.2.5
Control circuit terminals (common to all models)
[ 2 ] Terminal layout diagram (control circuit terminals)
FRN
E2
-
A, E, K, U
FRN
E2
-
C
Figure 2.2-8 Control circuit terminals layout
The following terminals will have high voltage when the power is ON.
Control terminals: AUX-contact (30A, 30B, 30C, Y5A, Y5C)
Insulation level
Contact output – control circuit : Enhanced insulation (overvoltage category II, degree of contamination 2)
Risk of electric shock exists
[ 3 ] Description of terminal functions (control circuit terminal)
Table 2.2.6-3 Functional Description of Control Circuit Terminals (continued)
Cla
s
s
if
ic
a
tio
n
Terminal
symbol
Terminal name
Functional description
D
igi
tal
i
npu
t
[EN1]
[EN2]
Enable input
(1) When terminals [EN1]-[PLC] or terminals [EN2]-[PLC] are OFF, the inverter output
transistors stop functioning. (Safe Torque Off: STO)
Be sure to operate terminals [EN1] and [EN2] simultaneously; otherwise an
ecf
alarm is
issued and the operation of the inverter will be disabled.
To enable the Enable function, remove the short bar.
(2) The input mode for terminals [EN1] and [EN2] is fixed to source. The mode cannot be
switched to sink.
(3) Short-circuit terminals [EN1]-[PLC] and [EN2]-[PLC] with short bars when the Enable
input function is not used. (Keep the short bar connected).
<EN terminal circuit specification>
PLC
Photo coupler
CM
<Control circuit block>
6.6 k
Ω
DC+24 V
EN1
6.6 k
Ω
EN2
Shorting
bar
[PLC]
Programma-
ble controller
signal power
source
(1) The terminal is used for connecting the output signal power source of the programmable
controller (rated voltage DC +24 V (power supply voltage fluctuation range: DC +22 to
+27 V) maximum 100 mA).
(2) The terminal can also be used for the power source for the load connected to the
transistor output. For details, refer to the page on transistor output.
Contact output
Enhanced insulation
(Max. 250 VAC overvoltage category II,
degree of contamination 2)
Contact output
Enhanced insulation
(Max. 250 VAC overvoltage category II,
degree of contamination 2)
Item
Min.
Max.
Operating
voltage
(SOURCE)
ON level
22 V
27 V
OFF level
0 V
2 V
Operating current at ON
(at input voltage 24 V)
-
4.5 mA
Allowable leak current at OFF
-
0.5 mA
2-12