Wire Replacement I/O (900 MHz): User Manual and Reference Guide
DI1 Pullup and DI2 Pullup
Setting
Description
l
Float - The internal resistor is not connected, allowing the connected
sensor to provide greater than 1.75 VDC for High and less than 1.75 VDC
for Low.
Terminal Menu:
(9) FGRIO Setup > (E) DI1 Pull Up/Down and (F) DI2 Pull Up/Down
Description:
Important!
: When toggling this coil between
ON
and
OFF
, the device
automatically reboots.
l
These parameters control the power-up states of the internal resistor (10
KΩ) connected to the Digital Inputs.
l
They can pull up, such as when using a closed-contact-to-GND switch
input, pull down so that unused inputs read "0" as DIs or ~0 as auxiliary
analogs, or float to not load analog inputs.
3.7.7 DO Bi-Stable
DO Bi-Stable
Setting
Description
Default Setting:
Constant
Options:
l
Constant
- The Digital Output remains on for as long as the I/O Master’s
associated Digital Input is connected to Ground.
l
When the I/O Master’s Digital Input is no longer grounded, the Digital
Output is OFF.
l
Auto-OFF
- The Digital Output remains on for the duration set in the
DO
Monostable Time
parameter or until the I/O Master’s associated Digital
Input is no longer grounded, whichever is shorter.
l
The Digital Output does not respond again to the I/O Master’s Digital
Input being grounded until the Digital Input has been disconnected from
Ground.
Terminal Menu:
(9) FGRIO Setup > ???
Description:
Controls how the Digital Outputs respond to ON commands.
If set to Auto-OFF, also set the DO Monostable Time parameter.
LUM0008AG Rev Sep-2015
Page 55 of 131
This document is the property of FreeWave Technologies, Inc. and contains proprietary information owned by
FreeWave®. This document cannot be reproduced in whole or in part by any means without written permission from
FreeWave Technologies, Inc.
Содержание FGR2-IO-IOE