![FreeWave FGR2-IO-IOE Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/freewave/fgr2-io-ioe/fgr2-io-ioe_user-manual-and-reference-manual_2331115101.webp)
Wire Replacement I/O (900 MHz): User Manual and Reference Guide
FGR2-IO-IOE Specifications
1: DI with pulsed 50 mA pull-up for long-lines or high noise
x
Output
2: High Current (2 A sink to GND) DOs with current sensing and
self-resetting protection
x
x
(3)
1: AO - 15 bits, 4-22mA, 0.1% FS Accuracy, also acts as 50mA
sensor power or DI
x
1: AO - 16 bits, 4-22mA, 0.1% FS Accuracy
x
Internal
1: Battery / Supply Voltage - 10 bits, 0-30 V, 1% FS Accuracy
x
1: Radio Temperature - 1° C units, -40° C to +70° C, 4° C
accuracy
x
Expandable I/O Stack up to 15 Expansion Modules
x
Diagnostics Interface
Connector
Separate 20-pin PCB header
Power Requirements
Operating Voltage
+6.0 to +30.0 VDC
Average Current (mA)
(currents shown with no
AO connections made)
Mode
+6.0 VDC
+12.0 VDC
+30.0 VDC
Transmit
800
380
170
Receive
90
55
40
Idle
24
16
8
Modbus
Linked
Lowpower =
4
10
7
5
Wire
Replacement
Linked
30
15
8
Product Safety
Standards
EN 60079-0:2012 + A11:2013 and EN 60079-15:2010
Labeling Information
II 3 G Ex nA IIC Gc
DEMKO 14 ATEX 1209313U
General Information
Operating Temperature
Range
-40°C to +75°C
LUM0008AG Rev Sep-2015