2. Configuring an I/O Master
Example
To map
Analog Output 1
of the I/O Master to
Analog Input 2
of the I/O Slave (serial # 930-
0004), entry
(5) Analog Out1
in the FGRIO Setup menu has a value of
2
. This is calculated by:
1. Verify the
Call Book
entry # of I/O Slave #930-0004.
Figure 8: Example of I/O Slave #
The entry number is
0
.
2. Use the table to find
Call Book
entry # 0.
3. View the column for I/O Slave
Analog Input #2
.
The value listed is
2
.
4. Enter a
2
for
Analog Output #1
of the I/O Master.
2.8.4 Sensor Power
Sensor Power
Setting
Description
Default Setting:
(0) Always On
Options:
l
(0) Always On
- Supplies continuous power to the VSNS port (Pin 7) of
the I/O Slave.
l
(1) Gated
- Controls the VSNS port of all I/O Slaves communicating with
the I/O Master.
l
Applying a voltage of greater than 1.75 VDC to the I/O Master’s Sensor
Power input port connects the VSNS port of every connected Short-
Range I/O Slave and I/O Slave to its supply voltage.
Page 44 of 131
LUM0008AG Rev Sep-2015