2. Configuring an I/O Master
Max Packet Size and Min Packet Size
Setting
Description
l
At a packet size of
Max = 2 Min = 2
, the maximum available count
would be 6Hz.
l
At a packet size of
Max = 9 Min = 9
, the maximum available count
would be 3Hz.
l
The pulse state must last for a 50% duty-cycle (that is, a 3Hz pulse needs
to last at least 166.6ms and a 6Hz pulse needs to last at least 83.3ms).
This table provides the available packet sizes in bytes for an I/O System by chartering the
Maximum Packet Size
and
Minimum Packet Size
setting when the
RF Data Rate
is set to
3
.
Combined Packet Size Definition with RF Data Rate of 3
Maximum Setting
Minimum
Setting
2
3
4
5
6
7
8
9
2
48
64
80
96
112
128
144
160
3
52
68
84
100
116
132
148
167
4
56
72
88
104
120
136
152
168
5
60
76
92
108
124
140
156
172
6
64
80
96
112
128
144
160
176
7
68
84
100
116
132
148
164
180
8
72
88
104
120
136
152
168
184
9
76
92
108
124
140
156
172
188
2.6.3 RF Data Rate
RF Data Rate
Setting
Description
Default Setting
(3) Normal
Options:
(2) High, (3) Normal
Terminal Menu:
(3) Edit Transmission Characteristics > (4) RF Data Rate
Setting:
l
The
RF Data Rate
must be set to
(3) Normal
in wire replacement I/O
systems.
l
In an integrated wire replacement I/O system, all radios, including any
serial radios in the network, must be set to an
RF Data Rate
of
3
.