background image

6

An ANSI approved manual shut-off valve and union must be installed
upstream of the heater within the fireplace cavity when rigid pipe is
used. Ensure that a sediment trap is installed upstream of the heater
(figure 4) within the structure’s piping system to prevent moisture and
contaminants from passing through the pipe to the heater controls and
burner. Failure to do so could prevent the heater from operating reliably.

The heater gas inlet connection is 3/8” NPT at the regulator, located
below the burner, in the right hand side of the heater. When tightening
up the joint to the regulator hold the regulator securely with a wrench to
prevent the regulator from moving. 

Turn on gas supply and test for gas leaks using a gas leak test solution
(also referred to as bubble leak solution).
NOTE: using a soapy water solution (50% dish soap, 50% water) is an
effective leak test solution, but it is not recommended, because the
soap residue that is left on the pipes/fittings can result in corrosion over
time. 

A. Light the appliance (refer to the lighting instructions label in the con-
trol compartment or on page 9).

B. Brush all joints and connections with the gas leak test solution to
check for leaks. If bubbles are formed, or gas odor is detected, turn the
gas control knob (off/pilot/on) to the “OFF” position. Either tighten or
refasten the leaking connection, then retest as described above.

C. When the gas lines are tested and leak free, be sure to rinse off the
leak testing solution.

D. Observe the individual tongues of flame on the burner. Make sure all
ports are open and producing flame evenly across the burner. If any
ports are blocked, or partially blocked, clean out the ports.

The heater regulator

controls the burner

pressure which

should be checked at

the pressure test

points located on the

control valve itself

(shown in figure 5)

for burner (manifold)

and regulator setting

pressure.

The valve is found on

the centre of the

appliance behind the

valve cover. 

Remove the cover

plate by unscrewing the four retaining screws. Release the test point

screws and ensure operating pressures are within the limits specified

in section 3 “Appliance data” on page 2 of these instructions.

The pressure should be checked with the gas heater burning and the

control set to high flame.

The pressure regulator on manual models is preset and locked to avoid

tampering. If the pressure is not as specified in the Appliance Data sec-

tion on page 2, replace the regulator with P/N FT/F730031 Replace the

test point screws after pressure measurement ensuring no gas leaks. 

The gap between the
spark electrode and the
pilot should be 1/8” to
3/16” to produce a good
spark.  There should be no
need to adjust this. If
under any circumstances
the piezo electric spark
fails, the pilot cannot be lit
manually.

The glass panel is supported by two
self-locking M6 screws, one on each
side of the fire. The glass panel must be
held in position while the screws are
inserted on each side - it is
recommended to seek assistance for
this operation. The screws should be
screwed in fully and then undone one
turn. to allow the glass panel to swing
open for access to the controls.

12.0 CHECKING THE GAS CONNECTIONS

IMPORTANT: HOLD HEATER REGULATOR WITH A
WRENCH TO PREVENT MOVEMENT WHEN CONNECTING
TO INLET PIPING.

Figure 4

13.0 GAS PRESSURE CHECK

Burner
(Manifold)
pressure

Regulator
pressure
setting

Figure 5

14.0 SPARK GAP

Figure 6

Spark gap

15.0 FITTING THE GLASS FACIA

11.0 CONNECTING A GAS LINE - continued

Содержание RADIUM F500080

Страница 1: ...ppliance WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIE...

Страница 2: ...ional as it may not be operating correctly Section Contents Page No 1 0 General Information 2 2 0 Inventory 2 3 0 Appliance Data 2 4 0 Important Safety Information 2 5 0 Codes 3 6 0 Combustion and Ven...

Страница 3: ...ed from The American National Standards Institute Inc 1430 Broadway New York NY 10018 or National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 Seller of unvented propane or natura...

Страница 4: ...s a combustible material or surface Clearance to the sides of the appliance are 4 but curtains drapes and other fabrics are not permitted within a distance of 20 of the appliance sides No such materia...

Страница 5: ...plate The bottom of the heater may be secured onto the lower mounting studs using the wingnuts or the hex nuts provided Mark the positions shown as Radium attachment points on the wall If the applianc...

Страница 6: ...or partially blocked clean out the ports The heater regulator controls the burner pressure which should be checked at the pressure test points located on the control valve itself shown in figure 5 for...

Страница 7: ...it strip off the burner pipes and clean thoroughly 8 Clean the in line restrictor pilot assembly and the burner tube Do not attempt to remove the pilot injector as this can cause damage 9 Re assemble...

Страница 8: ...ons and run at maximum setting for 15 minutes Position gas sample probe directly over a cata lyst via the outlet grille on top of the appliance Record the carbon diox ide CO2 concentration and then th...

Страница 9: ...nder section B above If you do not smell gas go to next step 6 The pilot is located on the left side behind the burner Figure 8 7 Depress control knob in and turn counterclockwise to the SPARK positio...

Страница 10: ...en fire is on high Poor gas flow to fire check pressure with fire on high If pressure is low remove any restriction in pipework or valve Check all isolators are adequately sized and fully open Check m...

Страница 11: ...G FAILURE TO POSITION THE PARTS IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS HEATER MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY As our policy is...

Страница 12: ...ALACI N AJUSTE MODIFICACI N REVISI N O MANTENIMIENTO INADECUADOS PUEDEN CAUSAR LESIONES O DA OS MATERIALES CONSULTE ESTE MANUAL SI NECESITA AYUDA O INFORMACI N ADICIONAL CONSULTE A UN INSTALADOR CALIF...

Страница 13: ...gina N 1 0 Informaci n general 13 2 0 Inventario 13 3 0 Especificaciones del aparato 13 4 0 Informaci n de seguridad importante 13 5 0 Normativa 14 6 0 Aire de combusti n y ventilaci n 14 7 0 Requisit...

Страница 14: ...Fuel Gas Code ANSI Z223 1 o NFPA54 que pueden obtenerse en The American National Standards Institute Inc 1430 Broadway New York NY 10018 o National Fire Protection Association Inc Batterymarch Park Qu...

Страница 15: ...ier material susceptible de decolorarse derretirse o deformarse al estar expuesto a un calor moderado debe considerarse como material o superficie combustible Debe dejarse un espacio libre de 4 en los...

Страница 16: ...er sometida a pruebas de estanqueidad antes de aplicar protecci n y o empotrar las tuber as y acoplamientos Una vez que haya seleccionado la posici n final de montaje del aparato teniendo en cuenta lo...

Страница 17: ...be comprobarse en los puntos de prueba de presi n ubicados en la v lvula de control en s ilustrado en la Figura 5 para ajustar la presi n del quemador colector y el regulador La v lvula se encue ntra...

Страница 18: ...del quemador desmonte los tubos del quemador y limpie a fondo 8 Limpie el restrictor en l nea el conjunto del piloto y el tubo del quemador No intente retirar el inyector del piloto puesto que podr a...

Страница 19: ...te al fabricante del equipo Encienda la chimenea siguiendo las instrucciones de uso y deje que funcione durante 15 minutos Ponga la sonda del analizador de gas directamente encima de un catalizador a...

Страница 20: ...n deseada Cierre el panel de acceso a la perilla de control Si la perilla no sale desista y llame inmediatamente a su t cnico de mantenimiento o a su compa a de gas Si despu s de varios intentos el p...

Страница 21: ...I DOBLE EL TERMOPAR PARA HACER QUE EL PILOTO SE MANTENGA ENCENDIDO La llama del piloto se reduce cuando Flujo defectuoso de gas al calentador compruebe la presi n con el calentador en Alto el calentad...

Страница 22: ...VERTENCIA EL NO UBICAR LAS PIEZAS EN LOS LUGARES SE ALADOS EN ESTOS DIAGRAMAS O LA UTILIZACI N DE PIEZAS NO HOMOLOGADAS OFICIALMENTE PARA EL USO CON ESTE CALENTADOR PUEDEN CAUSAR DA OS MATERIALES O LE...

Отзывы: