The space in the previous example is a confined space because the actual

BTU/Hr used is more than the maximum BTU/Hr the space can support.

You must provide additional fresh air.

Your options are:

a. 

Rework equations adding the space of adjoining room(s). If the extra

volume provides an unconfined space, then remove door or add ventilation

grills between rooms. Refer to National Fuel Gas Code, ANSI Z223.1,

Section 5.3.

b. 

Vent room directly to the outdoors. Refer to National Fuel Gas Code,

ANSI Z223.1, Section 5.3.

c. 

Install a lower BTU/Hr heater, to make the area an unconfined space.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can

support, then the space is an unconfined space. You will need no additional

fresh air ventilation for an unconfined space.

This appliance is designed to be wall-hung. Do not recess any part

of the appliance into the wall.

This Appliance may be installed in any room in a home except Bathrooms

- or areas where large amounts of steam are likely to be generated.

Installation in living rooms is common, however other rooms such as

kitchens, dining rooms and hallways are permitted, providing a suitable

natural gas supply is available, and rooms sizing and ventilation

requirements are strictly adhered to (see section 4).

The appliance is designed to be versatile, and as such will operate correctly

when exposed to normal gentle draughts experienced within the home. It is

not recommended, however that the appliance be installed in areas where

it is likely to be exposed to persistent strong draughts, that may be

generated by outside doors or windows, air vents etc. It is recommended

that the appliance should not be installed within 20” of any air vent.

Clearances to non-combustibles

Non-combustible surfaces are defined as brick, metal, marble, concrete

etc. and also a number of man-made materials impervious to flame. If in

doubt refer to the material manufacturer for further information before

proceeding with installation.

Clearances to the sides of the appliance are 4”. Clearance to the front of the

appliance is 20”. 

The back of the appliance may be installed directly onto a non-combustible

wall, providing the area behind the appliance is flat and does not interfere

with the various vent holes in the back panel of the appliance.

The appliance may be installed with or without a non-combustible hearth. If a

hearth is fitted, the size and design may be as desired.

A non-combustible shelf of any depth may be positioned above the appliance

provided it is no closer than 16” from the top of the appliance glass panel and

the wall above the appliance is non combustible.

Clearances to combustible materials

Combustible materials are defined as wood, fabrics, or other materials likely

to combust if exposed to flame. Generally, any material, which is likely to

discolour, melt or misshape when exposed to moderate heat, should be

considered as a combustible material or surface. 

Clearance to the sides of the appliance are 4” but curtains, drapes and other

fabrics are not permitted within a distance of 20” of the appliance sides. No

such materials are permitted directly above the appliance regardless of

distance. 

The minimum clearance to the ceiling above the appliance is 32” measured

from the top of the appliance glass panel.

Combustible materials should not be positioned directly in front of the

appliance within a distance of 40”.

Under no circumstances should any electrical equipment e.g. plasma screen

TV sets etc. be positioned on the wall above the appliance. The appliance is

designed to be wall mounted alone and not in conjunction with any type of

combustible fire surround. No combustible shelves should be positioned on

the wall above the appliance. It should be established that any mirrors or

picture frames etc. to be positioned on the wall above the   appliance are able

to withstand prolonged exposure to moderate heat and moisture before

proceeding with their installation.

The back of the appliance may be installed directly onto a combustible wall,

providing it is relatively flat and does not interfere with the various vent holes

in the back panel of the appliance. The wall must be structurally sound and

constructed from a material capable of withstanding moderate heat. Finished

plaster, conventional wall paper and dry-lined plasterboard are examples of

suitable materials. Materials such as flock, blown vinyl and embossed paper

which are sensitive to even small amounts of heat should be avoided as

scorching and or discoloration may occur over time.

If the appliance is to be mounted on a dry-lined wall or a timber framed

construction wall then the integrity and ability of the wall to carry the weight

of the appliance must be confirmed. It is important in these circumstances

that any vapor control barrier is not damaged, and that any structural

members of the house frame are not damaged.

The appliance may be positioned as close to a solid floor (i.e. stone, wooden

laminate etc.) as the particular design of fire frame permits, however it is not

permitted to install the appliance within 4” of carpet, rugs or fabric materials

of any kind. This dimension is measured vertically to the bottom of the

appliance frame.

4

6.0 COMBUSTION AND VENTILATION AIR - continued

WARNING: IF THE AREA IN WHICH THE HEATER MAY BE

OPERATED IS SMALLER THAN THAT DEFINED AS AN

UNCONFINED SPACE OR IF THE BUILDING IS OF

UNUSUALLY TIGHT CONSTRUCTION, PROVIDE ADEQUATE

COMBUSTION AND VENTILATION AIR BY ONE OF THE

METHODS DESCRIBED IN THE NATIONAL FUEL GAS CODE,

ANSI Z223.1/NFPA 54, SECTION 5.3 OR APPLICABLE LOCAL

CODES.

7.0 SITE REQUIREMENTS

4.

Compare the maximum BTU/Hr the space can support with the

actual amount of BTU/Hr used.

_______ BTU/Hr (max. the space can support)
_______ BTU/Hr (actual amount of BTU/Hr used)

Example:

61,440 

BTU/Hr (max. the space can support)

67,000       BTU/Hr (actual amount of BTU/Hr used)

WARNING: DO NOT USE A BLOWER INSERT, HEAT
EXCHANGER INSERT OR OTHER ACCESSORY NOT
APPROVED FOR USE WITH THIS HEATER.

Содержание RADIUM F500080

Страница 1: ...ppliance WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIE...

Страница 2: ...ional as it may not be operating correctly Section Contents Page No 1 0 General Information 2 2 0 Inventory 2 3 0 Appliance Data 2 4 0 Important Safety Information 2 5 0 Codes 3 6 0 Combustion and Ven...

Страница 3: ...ed from The American National Standards Institute Inc 1430 Broadway New York NY 10018 or National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 Seller of unvented propane or natura...

Страница 4: ...s a combustible material or surface Clearance to the sides of the appliance are 4 but curtains drapes and other fabrics are not permitted within a distance of 20 of the appliance sides No such materia...

Страница 5: ...plate The bottom of the heater may be secured onto the lower mounting studs using the wingnuts or the hex nuts provided Mark the positions shown as Radium attachment points on the wall If the applianc...

Страница 6: ...or partially blocked clean out the ports The heater regulator controls the burner pressure which should be checked at the pressure test points located on the control valve itself shown in figure 5 for...

Страница 7: ...it strip off the burner pipes and clean thoroughly 8 Clean the in line restrictor pilot assembly and the burner tube Do not attempt to remove the pilot injector as this can cause damage 9 Re assemble...

Страница 8: ...ons and run at maximum setting for 15 minutes Position gas sample probe directly over a cata lyst via the outlet grille on top of the appliance Record the carbon diox ide CO2 concentration and then th...

Страница 9: ...nder section B above If you do not smell gas go to next step 6 The pilot is located on the left side behind the burner Figure 8 7 Depress control knob in and turn counterclockwise to the SPARK positio...

Страница 10: ...en fire is on high Poor gas flow to fire check pressure with fire on high If pressure is low remove any restriction in pipework or valve Check all isolators are adequately sized and fully open Check m...

Страница 11: ...G FAILURE TO POSITION THE PARTS IN ACCORDANCE WITH THESE DIAGRAMS OR FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED WITH THIS HEATER MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY As our policy is...

Страница 12: ...ALACI N AJUSTE MODIFICACI N REVISI N O MANTENIMIENTO INADECUADOS PUEDEN CAUSAR LESIONES O DA OS MATERIALES CONSULTE ESTE MANUAL SI NECESITA AYUDA O INFORMACI N ADICIONAL CONSULTE A UN INSTALADOR CALIF...

Страница 13: ...gina N 1 0 Informaci n general 13 2 0 Inventario 13 3 0 Especificaciones del aparato 13 4 0 Informaci n de seguridad importante 13 5 0 Normativa 14 6 0 Aire de combusti n y ventilaci n 14 7 0 Requisit...

Страница 14: ...Fuel Gas Code ANSI Z223 1 o NFPA54 que pueden obtenerse en The American National Standards Institute Inc 1430 Broadway New York NY 10018 o National Fire Protection Association Inc Batterymarch Park Qu...

Страница 15: ...ier material susceptible de decolorarse derretirse o deformarse al estar expuesto a un calor moderado debe considerarse como material o superficie combustible Debe dejarse un espacio libre de 4 en los...

Страница 16: ...er sometida a pruebas de estanqueidad antes de aplicar protecci n y o empotrar las tuber as y acoplamientos Una vez que haya seleccionado la posici n final de montaje del aparato teniendo en cuenta lo...

Страница 17: ...be comprobarse en los puntos de prueba de presi n ubicados en la v lvula de control en s ilustrado en la Figura 5 para ajustar la presi n del quemador colector y el regulador La v lvula se encue ntra...

Страница 18: ...del quemador desmonte los tubos del quemador y limpie a fondo 8 Limpie el restrictor en l nea el conjunto del piloto y el tubo del quemador No intente retirar el inyector del piloto puesto que podr a...

Страница 19: ...te al fabricante del equipo Encienda la chimenea siguiendo las instrucciones de uso y deje que funcione durante 15 minutos Ponga la sonda del analizador de gas directamente encima de un catalizador a...

Страница 20: ...n deseada Cierre el panel de acceso a la perilla de control Si la perilla no sale desista y llame inmediatamente a su t cnico de mantenimiento o a su compa a de gas Si despu s de varios intentos el p...

Страница 21: ...I DOBLE EL TERMOPAR PARA HACER QUE EL PILOTO SE MANTENGA ENCENDIDO La llama del piloto se reduce cuando Flujo defectuoso de gas al calentador compruebe la presi n con el calentador en Alto el calentad...

Страница 22: ...VERTENCIA EL NO UBICAR LAS PIEZAS EN LOS LUGARES SE ALADOS EN ESTOS DIAGRAMAS O LA UTILIZACI N DE PIEZAS NO HOMOLOGADAS OFICIALMENTE PARA EL USO CON ESTE CALENTADOR PUEDEN CAUSAR DA OS MATERIALES O LE...

Отзывы: