Measuring Examples
7 - 9
MEASURING THREE-PHASE ON A DUAL
INPUT
Dual input measurements can be used for many applica-
tions. This example shows how to use these measure-
ments to determine phase rotation of a "Y" connected
three-phase system at a load center. Use alligator clips to
connect the ScopeMeter test tool to the three-phase sys-
tem connections.
Figure 7-8 Testing a Three-Phase System
WARNING
THE SETUP REQUIRES CONNECTING TEST LEADS
TO LIVE COMPONENTS OF A HIGH ENERGY CIRCUIT.
TO AVOID ELECTRIC SHOCK AND/OR EQUIPMENT
DAMAGE, USE CAUTION WHEN CONNECTING ALLI-
GATOR CLIPS TO LIVE COMPONENTS.
THE METAL JAWS OF ALLIGATOR CLIPS CAN CRE-
ATE A SHORT CIRCUIT BETWEEN CLOSELY SPACED
LIVE PARTS. AVOID MAKING CONNECTIONS TO
FEEDER CONDUCTORS OR BUS BARS AT ELEVATED
POTENTIALS. WHENEVER POSSIBLE, MAKE CON-
NECTIONS TO THE OUTPUT SIDE OF A CIRCUIT
BREAKER WHICH CAN PROVIDE BETTER SHORT CIR-
CUIT PROTECTION.
MAKE CONNECTIONS TO CIRCUIT BREAKERS BY
FIRST TURNING THE CIRCUIT BREAKER OFF. THEN
CONNECT THE ALLIGATOR CLIP TO THE BREAKER
OUTPUT TERMINAL VIA A SHORT PIECE OF INSU-
LATED WIRE AS SHOWN IN FIGURE 7-9.
91
Содержание 105 Series II
Страница 6: ...V ...
Страница 14: ...XIII Figure 2 Demo Board Non conductive surface ...
Страница 15: ...XIV 91 92 96 99 105 Users Manual ...
Страница 17: ...XVI 91 92 96 99 105 Users Manual ...
Страница 204: ...10 34 91 92 96 99 105 Users Manual Figure 10G 5 EXT mV menu MORE EXT mV ALERT ZERO FAST SMOOTH RESET READING ...
Страница 205: ...Appendixes 10 35 Figure 10G 6a MEASURE menu MORE MEASURE V dB TIME Hz See Figure 10G 6b ...
Страница 206: ...10 36 91 92 96 99 105 Users Manual Figure 10G 6b MEASURE menu MORE MEASURE V dB TIME Hz See Figure 10G 6a ...
Страница 212: ...10 42 91 92 96 99 105 Users Manual Figure 10G 13 SPECIAL FUNCTION menu MENU TEST MENU GENERATE MATH COMP 92 91 96 ...