66
Revision 10 – 1/09/2015
FTS 370d/w/r
Lighting Inspection (LI)
The Lighting Inspection (LI) menu allows
the user to test the alarm function of the
beacon in all modes, markers and the
photodiode dry contact.
The Lighting
Inspection
can
be
performed
as
an
automatic function (Auto Fast LI) or
manually.
The
manual
Lighting
Inspection has three modes available:
Manual Fast LI, Manual Staged LI and
Manual LI. Manual LI modes require the
unit to already be in the correct mode or
manually placed in the correct mode
before the test can be conducted.
The
system will ignore a test request until the
unit is placed in the correct corresponding
mode. A description of each LI mode is
provided in the following bullet points:
Automatic Fast LI cycles through all
test points and logs the results for
each. No interaction is required during
an Automatic LI. The previous test
results can be reviewed by selecting
Display Previous Results in the Auto
Fast LI menu.
Manual Fast LI mode tests the beacons
and markers simultaneously.
The
restore stage for each test is held for
user input.
Manual Staged LI mode tests each
beacon
and
marker
singly
and
sequentially.
The restore stage for
each test is held for user input.
Manual LI requires each test point to
be
selected.
Once
the
selected
function has been tested, the function
must be restored and the next test point
selected. This method continues for all
lighting components installed in the
system.
Note:
Some
monitoring
systems
require additional time between alarm
generation and receipt of the alarm.
Manual LI mode is recommended in this
instance.
Lighting
Inspection
(LI)
Display Previous
Resluts
"No Valid Results" Will Be Displayed If A Lighting Inspection Has Not Been
Performed.
Auto Fast LI
Begin Test (1 Button Inspection - Beacons & Markers Tested In
Parallel With No User Interaction.)
Yes /No
Yes Confirm?
Manual Fast LI
Begin Test (Beacons & Markers Tested in Parallel. Holds
Restore Stages For User Input.)
Yes /No
Yes Confirm?
Manual Staged LI
Begin Test (Beacons & Markers Tested In Each Mode Singly &
Sequentially. Holds Restore Stages for User Input.)
Yes /No
Yes Confirm?
Manual LI
Beacon Day Alarm
Alarm/Normal
Beacon White Night Alarm
Alarm/Normal
Beacon Red Night Alarm
Alarm/Normal
Beacon Comm. Alarm
Alarm/Normal
Marker Alarm
Alarm/Normal
Marker Comm. Alarm
Alarm/Normal
Photodiode Dry Contact Test
Alarm/Normal
Содержание VANGUARD FTS 370d
Страница 2: ......
Страница 36: ...24 Revision 10 1 09 2015 FTS 370d w r Figure 2 5 Marker Interface Wiring ...
Страница 50: ...38 Revision 10 1 09 2015 FTS 370d w r Figure 2 19 Typical D1 D2 System Wiring Diagram PHD 512 PHOTODIODE ...
Страница 54: ...42 Revision 10 1 09 2015 FTS 370d w r Figure 2 21 Typical Catenary System Wiring Diagram ...
Страница 94: ...This page intentionally left blank ...
Страница 96: ...84 Revision 10 1 09 2015 FTS 370d w r Figure 6 1 SC 370 AC Component Locations ...