62
Revision 10 – 1/09/2015
FTS 370d/w/r
Monitoring Config
The Monitoring Configuration option is
only available on the unit programmed as
System 1. This option selects the type of
monitoring for the system.
The options
include
Local
Ethernet
Configuration,
Primary Data Monitoring and Alternate
Data Monitoring.
Note:
Dry
contact
monitoring
is
available regardless of any additional
method selected to monitor the system.
Local Ethernet Configuration
The
options
available
in
the
Local
Ethernet Configuration provide a way to
configure System 1 to properly operate on
the connected network.
When System 1 utilizes a cellular modem
the settings should be as follows:
IP Address Mode: Static
IP Address: 192.168.1.11
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.1.10
The MAC Address is not editable.
Primary Data Monitoring
The options available in the Primary Data
Monitoring
submenu
are:
Disabled,
Cellular Eagle 2.0, RS 485 Modbus RTU,
Ethernet SNMP, Ethernet Modbus (RTU /
TCP) and Ethernet Eagle 2.0.
A brief
description of the application for each
method is listed in the following bullet
points:
Cellular
Eagle
-
selected when the
system is purchased with a cellular
modem and will be monitored by the
Flash Technology NOC.
RS 485 Modbus RTU -
used to connect
via
serial
cable
to
an
external
monitoring device on site that supports
Modbus protocol.
Ethernet SNMP -
used to connect via
Ethernet to a server that is able to
monitor SNMP traps.
Note:
See Appendix A for complete a
complete SNMP trap list.
Ethernet Modbus (RTU / TCP) -
used to
connect via Ethernet to an external
monitoring device on site or to a server
connected to the network that is able to
monitor Modbus devices.
Note:
See Appendix B for complete
Modbus specifications and map.
Ethernet Eagle -
selected when the
system is purchased with a SMART
card only and will be monitored
through a customer supplied Ethernet
connection
by Flash
Technology’s
NOC.
Note:
A static, public IP address is
required.
Network support will be
necessary on the customer supplied
connection and equipment.
Alternate Data Monitoring
Alternate Data Monitoring allows for a
secondary monitoring method. All options
available in the Primary Data Monitoring
menu are available in the Alternate Data
Monitoring menu.
Note:
Monitoring Options are mutually
exclusive. Example: If RS 485 Modbus
RTU is selected in either menu, it is
removed from the available options in
the other menu.
Ethernet
SNMP,
if
used,
must
be
selected as the Primary Data Monitoring
method.
Содержание VANGUARD FTS 370d
Страница 2: ......
Страница 36: ...24 Revision 10 1 09 2015 FTS 370d w r Figure 2 5 Marker Interface Wiring ...
Страница 50: ...38 Revision 10 1 09 2015 FTS 370d w r Figure 2 19 Typical D1 D2 System Wiring Diagram PHD 512 PHOTODIODE ...
Страница 54: ...42 Revision 10 1 09 2015 FTS 370d w r Figure 2 21 Typical Catenary System Wiring Diagram ...
Страница 94: ...This page intentionally left blank ...
Страница 96: ...84 Revision 10 1 09 2015 FTS 370d w r Figure 6 1 SC 370 AC Component Locations ...