22
OWNER’S MANUAL
NEUTON
™
PUMP MODULE
POINTS LIST, CONTINUED
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
Unoccupied
Setpoint Upper
Limit
Unoccupied setpoint upper limit
(maximum cooling) received from BAS
via comm or set through the BACview
keypad . Not adjustable at the Zone
Sensor ** .
BAV
AV:28
DEV:2402
unocc_setpt_
upper_limit_1
Water offset
above dew-point
The low water temperature limit as
an offset above the space dewpoint .
The controller clamps this value to
no less than 1 . Greater numbers
provide additional protection against
condensation .
BAV
AV:29
DEV:2402
water_temp_
dewpt_offset_1
water pump
signal
Status of signal delivered to water pump
from analog output # 3 . Status only,
not R/W . Note - 30% of 5 VDC or 1 .5
VDC constitutes an off command for
the pump . A signal of 0 VDC cause the
pump to run at a low speed .
BAV
AV:30
DEV:2402
pump_sig_1
zone 1 dewpoint
zone dewpoint calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:131
DEV:2402
zone_1_dewpt_1
zone 1 enthalpy
zone enthalpy calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:132
DEV:2402
zone_1_enth_1
zone 1 grains
zone grains calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:133
DEV:2402
zone_1_grains_1
zone 2 dewpoint
zone dewpoint calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:231
DEV:2402
zone_2_dewpt_1
zone 2 enthalpy
zone enthalpy calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:232
DEV:2402
zone_2_enth_1
zone 2 grains
zone grains calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:233
DEV:2402
zone_2_grains_1
zone 3 dewpoint
zone dewpoint calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:31
DEV:2402
zone_3_dewpt_1
zone 3 enthalpy
zone enthalpy calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:32
DEV:2402
zone_3_enth_1
zone 3 grains
zone grains calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:33
DEV:2402
zone_3_grains_1
zone 4 dewpoint
zone dewpoint calculated based on
the temperature and RH input from
(selectable) the Zone Sensor or BAS
comm input
BAV
AV:436
DEV:2402
zone_4_dewpt_1