OWNER’S MANUAL

NEUTON

 PUMP MODULE

POINTS LIST, CONTINUED

Name

Description

Type

Object ID

Device ID

Object Name

Exp:-

Num

I/O Type

Zone RH

RH value from Zone Sensor

ASVI

AI:3

DEV:2402

zone_rh_1

Zone Temp

Temperature value from Zone Sensor

ASVI

AI:4

DEV:2402

zone_temp_1

Condensate 

sensor

If a sensor is wired to input #1, 

and a contact closure is made, the 

condensation alarm is ON, and all 

outputs are OFF or 0 demand .

BBI

BI:1

DEV:2402

condensate_

sensor_1

0:01

Dry Con-

tact

Occupied (DC)

If a sensor or contact closure is wired to 

input #3, and the contact is made, the 

occupied setpoints are used .

BBI

BI:2

DEV:2402

occupied_dc_1

0:03

Dry Con-

tact

Pump CS

Status (only) of pump current switch if 

included and wired to input #2 .  Not an 

alarm point .

BBI

BI:3

DEV:2402

pump_current_

switch_1

0:02

Dry Con-

tact

chilled water 

valve signal

Status of signal delivered to chilled 

water valve from analog output # 1 .  

Status only, not R/W

BAV

AV:1

DEV:2402

chw_sig_1

CHW temp 

setpoint

The active CW temperature setpoint as 

adjusted by demand

BAV

AV:2

DEV:2402

chw_temp_

setpt_1

CO2 force OCC 

mode setpoint

If CO2 override is enabled, and the space 

CO2 exceeds this value, then Occupied 

Mode is ON .  The minimum setpoint 

value is 500 PPM .

BAV

AV:3

DEV:2402

co2_override_

setpt_1

Cooling Max 

Water Temp

The highest temperature desired for 

water temperature in cooling mode .  

Factory setting is 60°F .

BAV

AV:4

DEV:2402

chw_max_temp_1

Cooling Minimum 

pump output (%)

Cooling Minimum pump output (%) . 

Note: 0 - 100% pump demand is scaled 

to a 1 .5 to 5 VDC signal which is the 

operating range of the pump .

BAV

AV:6

DEV:2402

clg_min_pump_

output_1

Cooling Min 

Water Temp

The minimum water temperature will be 

the greater of <1° above space dewpoint, 

Cooling Min Water Temp parameter>

BAV

AV:5

DEV:2402

chw_min_temp_1

dewpoint alarm 

limit

If any (space dewpoint-dewpoint 

setpoint) exceeds the "dewpoint alarm 

limit" then the Zone high dewpoint alarm 

is ON

BAV

AV:34

DEV:2402

dewpoint_alarm_

limit_1

Heating Max 

Water Temp

Max water temp setpoint .  Default value 

is 130°F .  Above this range the risk of 

stratification quickly rises .

BAV

AV:7

DEV:2402

hw_max_temp_1

Heating Minimum 

pump output (%)

Heating Minimum pump output (%) 

Note: 0 - 100% pump demand is scaled 

to a 1 .5 to 5 VDC signal which is the 

operating range of the pump .

BAV

AV:9

DEV:2402

htg_min_pump_

output_1

Heating Min 

Water Temp

Heating Min Water Temp

BAV

AV:8

DEV:2402

hw_min_temp_1

hot water valve 

signal

Status of signal delivered to hot water 

valve from analog output # 2 .  Status 

only, not R/W

BAV

AV:10

DEV:2402

hw_sig_1

HW temp 

setpoint

The active HW temperature setpoint as 

adjusted by demand

BAV

AV:11

DEV:2402

hw_temp_setpt_1

max pump 

demand

The parameter will limit the pump speed 

for loops that do not require the full 

pump flow .

BAV

AV:12

DEV:2402

max_pump_

demand_1

Содержание Semco NEUTON

Страница 1: ...PROACTIVE CONTROL 1ST COST SAVINGS ENERGY SAVINGS OWNER S MANUAL CONTROLLED CHILLED BEAM PUMP MODULE...

Страница 2: ...the prior written permission of SEMCO LLC Patent pending SEMCO and the SEMCO logo are registered trademarks of SEMCO LLC All other trademarks are registered to their respective companies ZS Pro is ow...

Страница 3: ...RODUCTION CONFIGURATIONS NEUTON4 Dual Valve Pump Module NEUTON2 Single Valve Pump Module CLOSED CLOSED TO BEAMS FROM BEAMS Utilized as only cooling or only heating 2 pipe primary system supply return...

Страница 4: ...F primary loop water temperatures to optimal 58 F or 100 F chilled beam discharge temperatures which prevents cooling mode condensation and heating season heat stratification Each NEUTON can control u...

Страница 5: ...modulate as required to achieve the desired beam supply water temperature setpoint After a default time delay if the space cooling setpoint is not achieved or if it is exceeded beyond the deadband pa...

Страница 6: ...valve 5 Chilled water return 6 Hot water supply 7 Zone loop return connection 8 Chilled water supply 9 Hot water return 10 Zone supply water connection 11 Pete s plugs for pressure and flow measuremen...

Страница 7: ...h zone sensor and BAS if used On board controls specifically developed and optimized for chilled beam zone control plug and play All pipe connections use swivel half union adapters with face gasket de...

Страница 8: ...E DIMENSIONS NEUTON4 DUAL VALVE PUMP MODULE 7 5 16 10 1 2 10 1 2 21 9 16 7 11 16 4 1 8 3 13 16 21 3 8 1A FRONT 1C SIDE 1D BACK 1B TOP FIGURE 1 Dimensions of the NEUTON 4 Dual Valve Pump Module from th...

Страница 9: ...SIONS NEUTON2 SINGLE VALVE PUMP MODULE FIGURE 2 Dimensions of the NEUTON 2 Single Valve Pump Module from the front A top B side C and back D 20 3 4 17 1 2 4 1 8 7 11 16 3 13 16 10 1 2 10 1 2 7 5 16 2A...

Страница 10: ...repancy immediately notify SEMCO LLC Inspect the packages for signs of damage If damage is suspected contact SEMCO immediately If no visible damage is apparent the unit should be properly stored until...

Страница 11: ...n rung 103 See pages 12 13 Power Requirements Voltage 208 230 1 60 Amp Draw 1 2 FLA WARNING ELECTRIC WIRING MUST BE CARRIED OUT BY A QUALIFIED ELECTRICIAN Controls Wiring The controller RS 485 communi...

Страница 12: ...AUTO S S BY OTHER THAN SEMCO REMOVE FACTORY JUMPER IF TERMINALS ARE USED 0 10VDC MODULATING SIGNAL TO WATER PUMP 2 10VDC MODULATING SIGNAL TO CW VALVE ELECTRICAL SCHEMATIC NEUTON 4 Dual Valve Pump Mod...

Страница 13: ...VIDED FOR EXTERNAL AUTO S S BY OTHER THAN SEMCO REMOVE FACTORY JUMPER IF TERMINALS ARE USED 0 10VDC MODULATING SIGNAL TO WATER PUMP 2 10VDC MODULATING SIGNAL TO WATER VALVE ELECTRICAL SCHEMATIC NEUTON...

Страница 14: ...n the green LED is lit the zone is in an occupied state The ZS Pro Zone Sensor is designed for integration with the I O Zone 583 DDC controller Communications are established using the Rnet communicat...

Страница 15: ...ter to the local equipment for maintenance and commissioning Mounting Dimensions Standard 4 x 2 electrical box using provided 6 32 x 1 2 mounting screws The ZS Pro sensor is designed for integration w...

Страница 16: ...d values page 18 The sensor is in a timed override See To override the schedule page 17 The sensor s buttons are locked either because the control program specifies it or because a user locked them at...

Страница 17: ...ne in an occupied state for a length of time specified in the control program s Increment field 2 Press the button to incrementally increase the time The maximum length of time that you can override t...

Страница 18: ...Press the or button to adjust the value 2 Wait until the display returns to the home screen before you press any other buttons NOTE If the control program specifies that the value is not editable you...

Страница 19: ...ne Sensor and after limits applied by BAS Effective setpoint in use by controller BAV AV 21 DEV 2402 occ_htg_sp_1 Setpoint Cooling Unoccupied Setpoint Status of unoccupied cooling setpoint read from t...

Страница 20: ...t temperature desired for water temperature in cooling mode Factory setting is 60 F BAV AV 4 DEV 2402 chw_max_temp_1 Cooling Minimum pump output Cooling Minimum pump output Note 0 100 pump demand is s...

Страница 21: ...his point if the SEMCO wall mount Zone Sensor is not opted BAV AV 326 DEV 2402 bas_space_3_ temp_1 Space 4 RH from BAS BAS writes the space RH to this point if the SEMCO wall mount Zone Sensor is not...

Страница 22: ...AS comm input BAV AV 132 DEV 2402 zone_1_enth_1 zone 1 grains zone grains calculated based on the temperature and RH input from selectable the Zone Sensor or BAS comm input BAV AV 133 DEV 2402 zone_1_...

Страница 23: ..._rh_5_1 Zone Temp 1 BAV AV 701 DEV 2402 zone_temp_1_1 Zone Temp 2 BAV AV 702 DEV 2402 zone_temp_2_1 Zone Temp 3 BAV AV 703 DEV 2402 zone_temp_3_1 Zone Temp 4 BAV AV 704 DEV 2402 zone_tmp_4_1 Zone Temp...

Страница 24: ...DEV 2402 schedule_1 shutdown from BAS If this point is ON all signals are forced to OFF or 0 demand BBV BV 12 DEV 2402 shutdown_bas_1 Use BAS Inputs If this point is ON space temp and RH values are r...

Страница 25: ...d allowing a drop of water to escape Tighten the vent screw when complete No flow movement in actuator Check valve and actuator replacement to ensure valve and actuator are aligned properly Valve and...

Страница 26: ...0 10 Volt signal for this orientation is 0 volts NOTE The orientation of the notches on the center post at 9 00 6 00 and 3 00 o clock This is the proper orientation of the valve to the actuator at a 0...

Страница 27: ...the actuator is misaligned With the actuator removed from the valve Push in on the knob rotate it as far as it will go in the clockwise direction Remove the black knob and re insert it as shown in Fig...

Страница 28: ...ks of SEMCO LLC All other trademarks are registered to their respective companies SEMCO is a global leader in air management We specialize in the design and manufacture of a wide range of air climate...

Отзывы: