20
OWNER’S MANUAL
NEUTON
™
PUMP MODULE
POINTS LIST, CONTINUED
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
Zone RH
RH value from Zone Sensor
ASVI
AI:3
DEV:2402
zone_rh_1
Zone Temp
Temperature value from Zone Sensor
ASVI
AI:4
DEV:2402
zone_temp_1
Condensate
sensor
If a sensor is wired to input #1,
and a contact closure is made, the
condensation alarm is ON, and all
outputs are OFF or 0 demand .
BBI
BI:1
DEV:2402
condensate_
sensor_1
0:01
Dry Con-
tact
Occupied (DC)
If a sensor or contact closure is wired to
input #3, and the contact is made, the
occupied setpoints are used .
BBI
BI:2
DEV:2402
occupied_dc_1
0:03
Dry Con-
tact
Pump CS
Status (only) of pump current switch if
included and wired to input #2 . Not an
alarm point .
BBI
BI:3
DEV:2402
pump_current_
switch_1
0:02
Dry Con-
tact
chilled water
valve signal
Status of signal delivered to chilled
water valve from analog output # 1 .
Status only, not R/W
BAV
AV:1
DEV:2402
chw_sig_1
CHW temp
setpoint
The active CW temperature setpoint as
adjusted by demand
BAV
AV:2
DEV:2402
chw_temp_
setpt_1
CO2 force OCC
mode setpoint
If CO2 override is enabled, and the space
CO2 exceeds this value, then Occupied
Mode is ON . The minimum setpoint
value is 500 PPM .
BAV
AV:3
DEV:2402
co2_override_
setpt_1
Cooling Max
Water Temp
The highest temperature desired for
water temperature in cooling mode .
Factory setting is 60°F .
BAV
AV:4
DEV:2402
chw_max_temp_1
Cooling Minimum
pump output (%)
Cooling Minimum pump output (%) .
Note: 0 - 100% pump demand is scaled
to a 1 .5 to 5 VDC signal which is the
operating range of the pump .
BAV
AV:6
DEV:2402
clg_min_pump_
output_1
Cooling Min
Water Temp
The minimum water temperature will be
the greater of <1° above space dewpoint,
Cooling Min Water Temp parameter>
BAV
AV:5
DEV:2402
chw_min_temp_1
dewpoint alarm
limit
If any (space dewpoint-dewpoint
setpoint) exceeds the "dewpoint alarm
limit" then the Zone high dewpoint alarm
is ON
BAV
AV:34
DEV:2402
dewpoint_alarm_
limit_1
Heating Max
Water Temp
Max water temp setpoint . Default value
is 130°F . Above this range the risk of
stratification quickly rises .
BAV
AV:7
DEV:2402
hw_max_temp_1
Heating Minimum
pump output (%)
Heating Minimum pump output (%)
Note: 0 - 100% pump demand is scaled
to a 1 .5 to 5 VDC signal which is the
operating range of the pump .
BAV
AV:9
DEV:2402
htg_min_pump_
output_1
Heating Min
Water Temp
Heating Min Water Temp
BAV
AV:8
DEV:2402
hw_min_temp_1
hot water valve
signal
Status of signal delivered to hot water
valve from analog output # 2 . Status
only, not R/W
BAV
AV:10
DEV:2402
hw_sig_1
HW temp
setpoint
The active HW temperature setpoint as
adjusted by demand
BAV
AV:11
DEV:2402
hw_temp_setpt_1
max pump
demand
The parameter will limit the pump speed
for loops that do not require the full
pump flow .
BAV
AV:12
DEV:2402
max_pump_
demand_1