19
OWNER’S MANUAL
NEUTON™
POINTS LIST
KEYPAD
The BACview
6
keypad (
See Figure 9
) can be used to adjust setup parameters . The keypad can plug directly into the
bottom of the wall mount sensor (
See Figure 10
) or directly into the I/O Zone 583 Controller . If the CO
2
option on the
sensor is included, it may be necessary to plug the BACview
6
directly into the I/O Zone 583 controller, and disconnect
the wall mount sensor at the controller while the BACview is being used .
FIGURE 9.
BACview
6
Keypad (Optional - not
included with module)
FIGURE 10.
Plug the
BACview
6
keypad directly
into the bottom of the ZS
Pro Sensor zone controller .
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
Setpoint /
Cooling Occupied
Setpoint
Status of occupied cooling setpoint read
from the Zone Sensor and after limits
applied by BAS . Effective setpoint in use
by controller .
BAV
AV:20
DEV:2402
occ_clg_sp_1
Setpoint
/ Heating
Occupied
Setpoint
Status of occupied heating setpoint read
from the Zone Sensor and after limits
applied by BAS . Effective setpoint in use
by controller .
BAV
AV:21
DEV:2402
occ_htg_sp_1
Setpoint
/ Cooling
Unoccupied
Setpoint
Status of unoccupied cooling setpoint
read from the Zone Sensor and after
limits applied by BAS . Effective setpoint
in use by controller .
BAV
AV:22
DEV:2402
unocc_clg_sp_1
Setpoint
/ Heating
Unoccupied
Setpoint
Status of unoccupied heating setpoint
read from the Zone Sensor and after
limits applied by BAS . Effective setpoint
in use by controller .
BAV
AV:23
DEV:2402
unocc_htg_sp_1
Setpoint /
Cooling Setpoint
Adjust
not used - inaccessible Setblock block
internal value
BAV
AV:16
DEV:2402
clg_adj_1
Setpoint /
Heating Setpoint
Adjust
not used - inaccessible Setblock block
internal value
BAV
AV:19
DEV:2402
htg_adj_1
Setpoint /
Effective Cooling
Setpoint
not used - inaccessible Setblock block
internal value
BAV
AV:17
DEV:2402
eff_clg_sp_1
Setpoint /
Effective Heating
Setpoint
not used - inaccessible Setblock block
internal value
BAV
AV:18
DEV:2402
eff_htg_sp_1
water temp
Loop water temperature sensor wired to
analog input #4
BAI
AI:1
DEV:2402
water_temp_1
0:04
Thermistor
Zone CO2
CO2 value from Zone Sensor
ASVI
AI:2
DEV:2402
zone_co2_1