24
OWNER’S MANUAL
NEUTON
™
PUMP MODULE
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
Occ Status
If an occupied command BV:7 is ON, or
the occupied dry contact BI:2 is ON,
or if the CO2 override BV:3 is ON then
the status is occupied and occupied
setpoints are used
BBV
BV:8
DEV:2402
occ_status_1
Override On
Status of the occupancy override button
on the Zone Sensor
BBV
BV:9
DEV:2402
zs_override_on_1
Run Status
If there is a call for heating or cooling,
and there is no condensation or
shutdown command active, then the
pump will be on and either the cooling or
heating valve will modulate
BBV
BV:10
DEV:2402
run_status_1
Schedule
Communication based occupancy
command received from BAS schedule
or time clock .
BBV
BV:11
DEV:2402
schedule_1
shutdown from
BAS
If this point is ON, all signals are forced
to OFF or 0 demand
BBV
BV:12
DEV:2402
shutdown_bas_1
Use BAS Inputs
If this point is ON, space temp and RH
values are received from the BAS via
comm . If the Zone Sensor is not opted,
this point must be ON .
BBV
BV:14
DEV:2402
use_bas_inputs_1
CONDENSATION
ALARM
Status of digital input #1, BI:1 .
BALM
BV:504
DEV:2402
condensation_
alarm_1
UNIT ALARM
If any alarm is ON, unit alarm is ON .
BALM
BV:13
DEV:2402
unit_alm_1
WATER TEMP
ALARM
If the water temperature sensor is out of
range (<30, >200) the alarm is ON .
BALM
BV:515
DEV:2402
water_temp_
alarm_1
Zone high
dewpoint alarm
Zone high dewpoint alarm
BALM
BV:521
DEV:2402
zone_high_
dewpoint_
alarm_1
Zone high
temperature
alarm
Zone high temperature alarm
BALM
BV:519
DEV:2402
zone_high_temp_
alarm_1
Zone low
temperature
alarm
Zone low temperature alarm
BALM
BV:520
DEV:2402
zone_low_temp_
alarm_1
POINTS LIST, CONTINUED