OWNER’S MANUAL
NEUTON™
Name
Description
Type
Object ID
Device ID
Object Name
Exp:-
Num
I/O Type
Occupied
Setpoint Lower
Limit
Occupied setpoint lower limit (minimum
heating) received from BAS via comm or
set through the BACview keypad . Not
adjustable at the Zone Sensor ** .
BAV
AV:13
DEV:2402
occ_setpt_lower_
limit_1
Occupied
Setpoint Upper
Limit
Occupied setpoint upper limit (maximum
cooling) received from BAS via comm or
set through the BACview keypad . Not
adjustable at the Zone Sensor ** .
BAV
AV:14
DEV:2402
occ_setpt_upper_
limit_1
Program Version
Status of SEMCO program revision
BAV
AV:15
DEV:2402
prog_ver_1
Setpoint
Adjustment Limit
Range of setpoint adjustment at the Zone
Sensor received from BAS via comm or
set through the BACview keypad . Not
adjustable at the Zone Sensor ** .
BAV
AV:24
DEV:2402
setpt_adj_limit_1
Space 2RH from
BAS
BAS writes the space RH to this point, if
the SEMCO wall mount Zone Sensor ** is
not opted .
BAV
AV:225
DEV:2402
bas_space_2_
rh_1
Space 2 T from
BAS
BAS writes the space temperature to
this point, if the SEMCO wall mount Zone
Sensor ** is not opted .
BAV
AV:226
DEV:2402
bas_2_space_
temp_1
Space 3 RH from
BAS
BAS writes the space RH to this point, if
the SEMCO wall mount Zone Sensor ** is
not opted .
BAV
AV:325
DEV:2402
bas_space_3_
rh_1
Space 3 T from
BAS
BAS writes the space temperature to
this point, if the SEMCO wall mount Zone
Sensor ** is not opted .
BAV
AV:326
DEV:2402
bas_space_3_
temp_1
Space 4 RH from
BAS
BAS writes the space RH to this point, if
the SEMCO wall mount Zone Sensor ** is
not opted .
BAV
AV:425
DEV:2402
bas_space_4_
rh_1
Space 4 T from
BAS
BAS writes the space temperature to
this point, if the SEMCO wall mount Zone
Sensor ** is not opted .
BAV
AV:426
DEV:2402
bas_space_4_
temp_1
Space 5RH from
BAS
BAS writes the space RH to this point, if
the SEMCO wall mount Zone Sensor ** is
not opted .
BAV
AV:525
DEV:2402
bas_space_5_
rh_1
Space 5 T from
BAS
BAS writes the space temperature to
this point, if the SEMCO wall mount Zone
Sensor ** is not opted .
BAV
AV:526
DEV:2402
bas_space_5_
temp_1
Space RH from
BAS
BAS writes the space RH to this point, if
the SEMCO wall mount Zone Sensor ** is
not opted .
BAV
AV:25
DEV:2402
bas_space_rh_1
Space T from
BAS
BAS writes the space temperature to
this point, if the SEMCO wall mount Zone
Sensor ** is not opted .
BAV
AV:26
DEV:2402
bas_space_
temp_1
temp alarm limit
If any (space temperature-current
temperature setpoint) exceeds the
"temp alarm limit" then the Zone
high temperature alarm is ON .
If any (current temperature setpoint-
space temperature) exceeds the
"temp alarm limit" then the Zone low
temperature alarm is ON .
BAV
AV:35
DEV:2402
tempalarmlimit_1
Unoccupied
Setpoint Lower
Limit
Unoccupied setpoint lower limit
(minimum heating) received from BAS
via comm or set through the BACview
keypad . Not adjustable at the Zone
Sensor ** .
BAV
AV:27
DEV:2402
unocc_setpt_
lower_limit_1